1 Alarms
12360
Parameters:
Definitions:
Reactions:
Remedy:
Program Continuation:
12370
Parameters:
Definitions:
Reactions:
Remedy:
Program Continuation:
12380
Parameters:
Definitions:
Reactions:
Remedy:
1-152
Channel %1 block %2 dimension of parameter %3 incorrect
%1 = Channel number
%2 = Block number, label
%3 = Source string
The following possibilities of error must be checked:
• The current parameter is an array, but the formal parameter is a variable
• The current parameter is a variable, but the formal parameter is an array
• The current and formal parameters are arrays, but not with the dimensions to be
defined.
- Correction block
- Interface signals are set.
- Alarm display.
Press the NC Stop key and select the function "Correction block" with the softkey PRO-
GRAM CORRECT. The correction pointer positions on the incorrect block. Correct the NC
part program in accordance with the cause of error as listed above.
Clear alarm with NC START or RESET key and continue the program.
Channel %1 block %2 range of values %3 not permissible
%1 = Channel number
%2 = Block number, label
%3 = Source string
A variable has been initialized with a value range outside an initialization block. The defi-
nition of program-global variables is allowed only in special initialization blocks. These
variables can be initialized with a value range.
- Correction block
- Interface signals are set.
- Alarm display.
Press the NC Stop key and select the function "Correction block" with the softkey PRO-
GRAM CORRECT. The correction pointer positions on the incorrect block.
Remove the value range specification (begins with the keyword OF) or define the variable
as a global variable in the initialization block and initialize it with a value range.
Clear alarm with NC START or RESET key and continue the program.
Channel %1 block %2 maximum memory capacity reached
%1 = Channel number
%2 = Block number, label
The data definitions in this block cannot be processed because the maximum available
memory for creating the data has been filled, or because the data block cannot accommo-
date any further data.
The alarm can also occur if several subroutine calls are executed in sequence and no
block with an effect on the machine is generated (motion, dwell, M function).
- Correction block
- Interface signals are set.
- Alarm display.
Please inform the authorized personnel/service department. Reduce the number of vari-
ables, reduce the size of arrays, or increase the capacity of the data management sys-
tem.
• If new macro definitions are to be introduced -> increase machine data 18160
MM_NUM_USER_MACROS
 Siemens AG, 2004. All rights reserved
SINUMERIK 840D/840Di/810D Diagnostics Guide (DA), 10.04 Edition