Name/Value
04.21
Fault word 1
(04.120
Bit
Standard ctrl
program)
0
SHORT CIRC
1
OVERCURRENT
2
DC OVERVOLT
3
ACS800 TEMP
4
EARTH FAULT
5
THERMISTOR
6
MOTOR TEMP
7
SYSTEM_FAULT
8
UNDERLOAD
9
OVERFREQ
10
Reserved
11
Reserved
12
Reserved
13
Reserved
14
Reserved
15
Reserved
0000h...FFFFh
Description
ACS800-compatible fault word 1.
The bit assignments of this word correspond to FAULT
WORD 1 in the ACS800. Parameter
word compatibility
determines whether the bit assignments
are according to the ACS800 Standard or ACS800 System
control program.
Each bit can indicate several ACS880 events as listed below.
This parameter is read-only.
ACS800 fault name
=
ACS800
(04.120
=
ACS800
System ctrl
program)
SHORT CIRC
OVERCURRENT
DC OVERVOLT
ACS800 TEMP
EARTH FAULT
MOTOR TEMP M
MOTOR TEMP
SYSTEM_FAULT
UNDERLOAD
OVERFREQ
MPROT SWITCH
CH2 COMM LOSS
SC (INU1)
SC (INU2)
SC (INU3)
SC (INU4)
ACS800-compatible fault word 1.
04.120 Fault/Warning
ACS880 events indicated by this bit
(see
Fault
tracing, page 565)
2340
2310
3210
2381, 4210, 4290, 42F1, 4310,
2330, 2392,
3181
4981
4982
6481, 6487, 64A1, 64A2, 64A3, 64B1, 64E1,
6881, 6882, 6883,
6885
-
7310
9081
7582
2340
(XXYY YY01)
2340
(XXYY YY02)
2340
(XXYY YY03)
2340
(XXYY YY04)
Parameters 159
Def/FbEq16
-
4380
1 = 1