386 Parameters
No.
Name/Value
58.03
Node address
0...255
58.04
Baud rate
9.6 kbps
19.2 kbps
38.4 kbps
57.6 kbps
76.8 kbps
115.2 kbps
58.05
Parity
8 NONE 1
8 NONE 2
8 EVEN 1
8 ODD 1
58.06
Communication
control
Enabled
Refresh settings
Silent mode
Description
Defines the node address of the drive on the fieldbus link.
Values 1...247 are allowable. Two devices with the same
address are not allowed on-line.
Changes to this parameter take effect after the control unit is
rebooted or the new settings validated by parameter
Communication
control.
Node address (values 1...247 are allowable).
Selects the transfer rate of the fieldbus link.
Changes to this parameter take effect after the control unit is
rebooted or the new settings validated by parameter
Communication
control.
9.6 kbit/s.
19.2 kbit/s.
38.4 kbit/s.
57.6 kbit/s.
76.8 kbit/s.
115.2 kbit/s.
Selects the type of parity bit and the number of stop bits.
Changes to this parameter take effect after the control unit is
rebooted or the new settings validated by parameter
Communication
control.
Eight data bits, no parity bit, one stop bit.
Eight data bits, no parity bit, two stop bits.
Eight data bits, even parity bit, one stop bit.
Eight data bits, odd parity bit, one stop bit.
Validates any changes in the EFB settings, or activates silent
mode.
Normal operation.
Validates any changed EFB configuration settings. Reverts
automatically to Enabled.
Activates silent mode (no messages are transmitted).
Silent mode can be terminated by activating the
settings
selection of this parameter.
Def/FbEq16
1
58.06
1 = 1
19.2 kbps
58.06
2
3
4
5
6
7
8 EVEN 1
58.06
0
1
2
3
Enabled
0
1
2
Refresh