596 Fault tracing
Code
Fault
(hex)
64E1
Kernel overload
6581
Parameter system
65A1
FBA A parameter
conflict
65A2
FBA B parameter
conflict
65B1
Reference source
parametrization
6681
EFB comm loss
Programmable fault:
58.14 Communication loss
action
6682
EFB config file
6683
EFB invalid
parameterization
6684
EFB load fault
6881
Text data overflow
6882
Text 32-bit table
overflow
6883
Text 64-bit table
overflow
6885
Text file overflow
7080
Option module comm
loss
Cause
Operating system error.
Parameter load or save failed.
The drive does not have a
functionality requested by
PLC, or requested functionality
has not been activated.
The drive does not have a
functionality requested by
PLC, or requested functionality
has not been activated.
A reference source is
simultaneously connected to
multiple parameters with
different units.
Communication break in
embedded fieldbus (EFB)
communication.
Embedded fieldbus (EFB)
configuration file could not be
read.
Embedded fieldbus (EFB)
parameter settings
inconsistent or not compatible
with selected protocol.
Embedded fieldbus (EFB)
protocol firmware could not be
loaded.
Version mismatch between
EFB protocol firmware and
drive firmware.
Internal fault.
Internal fault.
Internal fault.
Internal fault.
Communication between drive
and an option module is lost.
What to do
Reboot the control unit (using parameter
96.08 Control board
boot) or by cycling
power. If the problem persists, contact
your local ABB representative.
Try forcing a save using parameter
Parameter save
manually. Retry.
Check PLC programming.
Check settings of parameter groups
Fieldbus adapter (FBA)
settings.
Check PLC programming.
Check settings of parameter groups
Fieldbus adapter (FBA)
settings.
See
A6DA Reference source
parametrization
(page 576).
Check the status of the fieldbus master
(online/offline/error etc.).
Check cable connections to the XD2D
connector on the control unit.
Contact your local ABB representative.
Check the settings in parameter group
Embedded
fieldbus.
Contact your local ABB representative.
Reset the fault. Contact your local ABB
representative if the fault persists.
Reset the fault. Contact your local ABB
representative if the fault persists.
Reset the fault. Contact your local ABB
representative if the fault persists.
Reset the fault. Contact your local ABB
representative if the fault persists.
See
A798 Encoder option comm loss
(page 578).
96.07
50
and
51 FBA A
50
and
54 FBA B
58