Code
Warning
(hex)
A782
FEN temperature
A791
Brake resistor
A793
BR excess
temperature
A794
BR data
0000 0001 Resistance value too low.
0000 0002 Thermal time constant not
0000 0003 Maximum continuous power
A797
Speed feedback
configuration
Cause
Error in temperature
measurement when
temperature sensor (KTY or
PTC) connected to encoder
interface FEN-xx is used.
Error in temperature
measurement when KTY
sensor connected to encoder
interface FEN-01 is used.
Brake resistor broken or not
connected.
Brake resistor temperature has
exceeded warning limit defined
by parameter
43.12 Brake
resistor warning
limit.
Brake resistor data has not
been given.
given.
not given.
Speed feedback configuration
has changed.
0001 Adapter not found in specified
slot.
0002 Detected type of interface
module does not match
parameter setting.
0003 Logic version too old.
0004 Software version too old.
Fault tracing 577
What to do
Check that parameter
35.11 Temperature
1 source
/
35.21 Temperature 2 source
setting corresponds to actual encoder
interface installation.
Check the settings of parameters
and 91.24. Check that the corresponding
module is activated in parameters
91.11...91.14. Use parameter
Encoder parameter refresh
any changes in the settings.
FEN-01 does not support temperature
measurement with KTY sensor. Use PTC
sensor or other encoder interface
module.
Check that a brake resistor has been
connected.
Check the condition of the brake resistor.
Stop drive. Let resistor cool down.
Check resistor overload protection
function settings (parameter group
Brake
chopper).
Check warning limit setting, parameter
43.12 Brake resistor warning
Check that the resistor has been
dimensioned correctly.
Check that braking cycle meets allowed
limits.
One or more of the resistor data settings
(parameters 43.08...43.10) is incorrect.
The parameter is specified by the
auxiliary code.
Check value of 43.10.
Check value of 43.08.
Check value of 43.09.
Check the auxiliary code (format XXYY
ZZZZ). "XX" specifies the number of the
encoder interface module (01:
91.11/91.12, 02: 91.13/91.14), "YY"
specifies the encoder (01:
configuration, 02:
93 Encoder 2
configuration). "ZZZZ" indicates the
problem (see actions for each code
below).
Check module location
(91.12
Check the module type
against status
(91.02
or 91.03).
Contact your local ABB representative.
Contact your local ABB representative.
91.21
91.10
to validate
43
limit.
92 Encoder 1
or 91.14).
(91.11
or 91.13)