332 Parameters
No.
Name/Value
35.60
Cable temperature
0.0 ... 200.0%
35.61
Cable nominal
current
0.00 ... 10000.00 A
35.62
Cable thermal rise
time
0 s
1...50000 s
Description
Shows the calculated temperature of the motor cable. See
section
Thermal protection of motor cable
102% = overtemperature warning
overload)
106% = overtemperature fault
This parameter is read-only.
Calculated temperature of motor cable.
Specifies the continuous current of the motor cable for the
thermal protection function in the control program.
WARNING! The value entered in this parameter must
be limited according to all factors affecting the
loadability of the cable, such as ambient temperature,
cabling arrangement, and shrouding. Refer to the technical
data from the cable manufacturer.
Continuous current-carrying capacity of motor cable.
Specifies the thermal time of the motor cable for the thermal
protection function in the control program. This value is
defined as the time to reach 63% of the nominal cable
temperature when the cable is loaded with nominal current
(parameter
35.61 Cable nominal
0 s = Thermal protection of motor cable disabled
Refer to the technical data from the cable manufacturer.
Cable current
100%
Temperature rise
100%
63%
Cable thermal time
Thermal protection of motor cable disabled.
Motor cable thermal time constant.
(page 119).
(A480 Motor cable
(4000 Motor cable
overload)
current).
Def/FbEq16
0.0%
1 = 1%
10000.00 A
1 = 1 A
1 s
Time
Time
1 = 1 s
1 = 1 s