User Load Curve - ABB +N5600 Firmware Instructions

Single drive
Table of Contents

Advertisement

338 Parameters
No.
Name/Value
36.48
AL2 80 to 90%
0.00 ... 100.00%
36.49
AL2 over 90%
0.00 ... 100.00%
36.50
AL2 reset date
-
36.51
AL2 reset time
-
37

37 User load curve

37.01
ULC output status
word
Bit
Name
0
Under load limit
1
Reserved
2
Over load limit
3...15
Reserved
000b ... 101b
37.02
ULC supervision
signal
Not selected
Motor current %
Motor torque %
Output power % of
motor nominal
Other
37.03
ULC overload
actions
Disabled
Warning
Fault
Warning/Fault
Description
Displays the percentage of samples recorded by amplitude
logger 2 that fall between 80 and 90%.
Amplitude logger 2 samples between 80 and 90%.
Displays the percentage of samples recorded by amplitude
logger 2 that exceed 90%.
Amplitude logger 2 samples over 90%.
Displays the date on which amplitude logger 2 was last reset. -
Last reset date of amplitude logger 2.
Displays the time at which amplitude logger 2 was last reset.
Last reset time of amplitude logger 2.
Settings for user load curve.
See also section
User load curve
Displays the status of the monitored signal. (The status word
is independent of the actions and delays selected by
parameters 37.03, 37.04,
This parameter is read-only.
Information
1 = Monitored signal is below the underload curve
1 = Monitored signal is above the overload curve
Status of the monitored signal.
Selects the signal to be monitored. The function compares
the absolute value of the signal against the load curve.
No signal selected (monitoring disabled).
01.07 Motor current
(see page 152).
01.10 Motor torque
(see page 152).
01.15 Output power % of motor nom
Source selection (see
Terms and abbreviations
Selects how the drive reacts if the absolute value of the
monitored signal stays above the overload curve for longer
than the value of
37.41 ULC overload
No action taken.
The drive generates a warning
warning).
Drive trips on
8002 ULC overload
The drive generates a warning
if the signal stays continuously above the overload curve for
half of the time defined by
The drive trips on
8002 ULC overload fault
continuously above the overload curve for the time defined by
37.41 ULC overload
timer.
(page 119).
37.41
and 37.42.)
(see page 153).
on page 148). -
timer.
(A8BE ULC overload
fault.
(A8BE ULC overload
37.41 ULC overload
timer.
if the signal stays
Def/FbEq16
0.00%
1 = 1%
0.00%
1 = 1%
-
-
-
-
1 = 1
Not selected
0
2
3
4
Disabled
0
1
2
warning)
3