7. Switch on the power to the drive/inverter unit.
8. Enter the number of inverter modules present into parameter
mode.
9. Reset all faults and start the drive/inverter unit. The maximum current is now
automatically limited according to the new inverter configuration. A mismatch
between the number of detected modules (95.14) and the value set in
generate a fault.
After all modules have been reinstalled, parameter
reset to 0 to disable the reduced run function. In case the inverter is equipped with a
charging circuit, the charging monitoring must be reactivated for all modules. If the
Safe torque off (STO) function is in use, an acceptance test must be performed (see
the hardware manual of the drive/inverter unit for instructions).
Settings
Parameters
06.17

du/dt filter support

With an external du/dt filter connected to the output of the drive, bit 13 of
options word 1
must be switched on. The setting limits the output switching
frequency, and forces the drive/inverter module fan to full speed. Note that the setting
is not to be activated with inverter modules with internal du/dt filters.
Settings
Parameter
95.20 HW options word 1

Sine filter support

The control program has a setting that enables the use of sine filters (available
separately from ABB and others).
With an ABB sine filter connected to the output of the drive, bit 1 of
settings
must be switched on. The setting limits the switching and output frequencies
to
• prevent the drive from operating at filter resonance frequencies, and
• protect the filter from overheating.
With a custom sine filter, bit 3 of
(The setting does not limit the output frequency.) Additional parameters must be set
according to the properties of the filter as listed below.
Settings
For both ABB and custom filters: Parameter
(page 168) and
95.13...95.14
95.15 Special HW settings
95.13 Reduced run mode
(page 476).
(page 477).
95.15 Special HW settings
Program features 129
95.13 Reduced run
95.13
must be
95.20 HW
95.15 Special HW
must be switched on.
(page 476).