500 Parameters
No.
Name/Value
99.15
Motor polepairs
calculated
0...1000
99.16
Motor phase order
U V W
U W V
99.18
Sine filter
inductance
0.000 ...
100000.000 mH
Description
Calculated number of pole pairs in the motor.
Number of pole pairs.
Switches the rotation direction of motor. This parameter can
be used if the motor turns in the wrong direction (for example,
because of the wrong phase order in the motor cable), and
correcting the cabling is considered impractical.
Notes:
• Changing this parameter does not affect speed reference
polarities, so positive speed reference will rotate the motor
forward. The phase order selection just ensures that
"forward" is in fact the correct direction.
• After changing this parameter, the sign of encoder
feedback (if any) must be checked. This can be done by
setting parameter
90.41 Motor feedback selection
Estimate, and comparing the sign of
control
to
90.10 Encoder 1 speed
speed). If the sign of the measurement is incorrect, the
encoder wiring must be corrected or the sign of
Motor gear numerator
Normal.
Reversed rotation direction.
Defines the inductance of a custom sine filter, ie. when
parameter
95.15 Special HW settings
Note: For an ABB sine filter
this parameter is set automatically and should not be
adjusted.
Inductance of custom sine filter.