398 Parameters
No.
Name/Value
60.19
M/F comm
supervision sel 1
Bit
Name
0
Follower 1
1
Follower 2
...
...
15
Follower 16
0000h...FFFFh
60.20
M/F comm
supervision sel 2
Bit
Name
0
Follower 17
1
Follower 18
...
...
15
Follower 32
0000h...FFFFh
Description
Parameters
60.19...60.28
the master on a D2D (drive-to-drive) link, implemented by
application programming. See parameters
communication port
and
(IEC 61131-3) application programming manual
(3AUA0000127808 [English]).
In the master, parameters
and
60.20 M/F comm supervision sel 2
that are monitored for loss of communication.
This parameter selects which followers (out of followers
1...16) are monitored. Each of the selected followers is polled
by the master. If no reply is received, the action specified in
60.09 M/F comm loss function
The status of communication is shown by
communication status 1
2.
Description
1 = Follower 1 is polled by the master.
1 = Follower 2 is polled by the master.
...
1 = Follower 16 is polled by the master.
Selection of followers for D2D communication supervision (1). 1 = 1
Selects which followers (out of followers 17...32) are
monitored for loss of communication. See parameter
M/F comm supervision sel
Description
1 = Follower 17 is polled by the master.
1 = Follower 18 is polled by the master.
...
1 = Follower 32 is polled by the master.
Selection of followers for D2D communication supervision (2). 1 = 1
are only effective when the drive is
60.01 M/F
60.03 M/F
mode, and Drive
60.19 M/F comm supervision sel 1
specify the followers
is taken.
62.37 M/F
and
62.38 M/F communication status
1.
Def/FbEq16
-
-