34 Quick start-up guide
Set motor nominal frequency.
Set motor nominal speed.
Set motor nominal power.
Set motor cos
.
Φ
Note: This value is not mandatory, but can
be entered to improve the control accuracy. If
not known, enter the value as zero (0).
Set sine filter data.
• Check
95.15 Special HW settings
• If ABB official filter is used, set bit1 ABB
sine filter = 1.
• If sine filter is supplied by other vendor,
set bit 3 Custom sine filter = 1.
• If no filter is used, make sure both bit1
and bit3 are set to 0.
• For filters other than ABB filter, it is also
important to provide filter data using
parameters
99.18
Set used transformation ratio based on step-
up transformer tapping.
Set desired drive control interface.
Note: By default, the drive is configured to
start/stop from I/O interface. Other options
are available, including Fieldbus.
Set desired drive start trigger type.
Drive will react on edge or level status of
user start command based on this parameter
setting.
If default control interface is used, select the
source for the drive control signal.
Note: By default, the drive starts/stops
according to the status of digital input DI1
(0 = Stop, 1 = Start).
Select desired motor stop mode: ramp or
coast.
and 99.19.
3 – Drive control interface settings
99.08 Motor nominal frequency
99.09 Motor nominal speed
99.10 Motor nominal power
99.11 Motor nominal cos Φ
95.15 Special HW settings
99.18 Sine filter inductance
99.19 Sine filter capacitance
95.40 Transformation ratio
20.01 Ext1 commands
20.02 Ext1 start trigger type
20.03 Ext1 in1 source
21.03 Stop mode