330 Parameters
No.
Name/Value
35.51
Motor load curve
I/I
N
(%)
150
100
50
35.52
50 ... 150%
35.52
Zero speed load
50 ... 150%
35.53
Break point
1.00 ... 500.00 Hz
Description
Defines the motor load curve together with parameters
Zero speed load
and
35.53 Break point.
used by the motor thermal protection model to estimate the
motor temperature.
When the parameter is set to 100%, the maximum load is
taken as the value of parameter
(higher loads heat up the motor). The load curve level should
be adjusted if the ambient temperature differs from the
nominal value set in
35.50 Motor ambient
I = Motor current
I
= Nominal motor current
N
35.51
35.53
Maximum load for the motor load curve.
Defines the motor load curve together with parameters
Motor load curve
and
35.53 Break
maximum motor load at zero speed of the load curve. A
higher value can be used if the motor has an external motor
fan to boost the cooling. See the motor manufacturer's
recommendations.
See parameter
35.51 Motor load
Zero speed load for the motor load curve.
Defines the motor load curve together with parameters
Motor load curve
and
35.52 Zero speed
break point frequency of the load curve i.e. the point at which
the motor load curve begins to decrease from the value of
parameter
35.51 Motor load curve
parameter
35.52 Zero speed
See parameter
35.51 Motor load
Break point for the motor load curve.
The load curve is
99.06 Motor nominal current
temperature.
Drive output
frequency
point. Defines the
curve.
load. Defines the
towards the value of
load.
curve.
Def/FbEq16
35.52
100%
1 = 1%
35.51
100%
1 = 1%
35.51
45.00 Hz
See par.
46.02