ABB +N5600 Firmware Instructions page 597

Single drive
Table of Contents

Advertisement

Code
Fault
(hex)
7081
Control panel loss
Programmable fault:
Communication loss
action
7082
Ext I/O comm loss
00 0001 Communication with module
00 0002 Module not found.
00 0003 Configuration of module failed.
00 0004 Configuration of module failed.
7083
Panel reference
conflict
7084
Panel/PC tool version
conflict
7085
Incompatible option
module
7121
Motor stall
Programmable fault:
Stall function
Cause
Control panel (or PC tool) has
stopped communicating.
49.05
The I/O extension module
types specified by parameters
do not match the detected
configuration.
failed.
Use of saved control panel
reference in multiple control
modes attempted.
The current version of the
control panel and/or PC tool
does not support a function.
(For example, older panel
versions cannot be used as a
source of external reference.)
Option module not supported.
(For example, type Fxxx-xx-M
fieldbus adapter modules are
not supported.)
Motor is operating in stall
region because of e.g.
31.24
excessive load or insufficient
motor power.
Fault tracing 597
What to do
Check PC tool or control panel
connection.
Check control panel connector.
Disconnect and reconnect the control
panel.
Check the auxiliary code. The code
specifies the I/O port used as follows: 0:
Panel, 1: Fieldbus interface A, 2:
Fieldbus interface B, 3: Ethernet, 4:
D2D/EFB port).
Check the auxiliary code (format
XXYY YYYY). "XX" specifies the number
of the I/O extension module (01:
parameter group
14 I/O extension
module
1, 02:
15 I/O extension module
03:
16 I/O extension module
"YY YYYY" indicates the problem (see
actions for each code below).
Check that the module is properly seated
in its slot.
Check that the module and the slot
connector is not damaged.
Try installing the module into another
slot.
Check the type and location settings of
the modules (parameters 14.01/14.02,
15.01/15.02
or 16.01/16.02).
Check that the module is properly seated
in its slot.
Check that the module and the slot
connector is not damaged.
Try installing the module into another
slot.
The control panel reference can only be
saved for one reference type at a time.
Consider the possibility of using a copied
reference instead of saved reference
(see the reference selection parameter).
Update control panel and/or PC tool.
Contact your local ABB representative if
necessary.
Check the auxiliary code. The code
specifies the interface to which the
unsupported module is connected:
1: Fieldbus interface A, 2: Fieldbus
interface B.
Replace the module with a supported
type.
Check motor load and drive ratings.
Check fault function parameters.
2,
3).

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents