ABB +N5600 Firmware Instructions page 311

Single drive
Table of Contents

Advertisement

No.
Name/Value
31.37
Ramp stop
supervision
0...300%
31.38
Ramp stop
supervision delay
0...32767 s
31.40
Disable warning
messages
Bit
Fault
0
Overvoltage
1
Reserved
2
Encoder 1
3
Encoder 2
4
CU (Control unit) battery
5...15
Reserved
0000b...1101b
31.42
Overcurrent fault
limit
0.00 ... 30000.00 A
Description
Parameters
31.37 Ramp stop supervision
stop supervision
delay, together with
rate, provide a supervision function for normal (ie. non-
emergency) ramp stopping.
The supervision is based on either
• observing the time within which the motor stops, or
• comparing the actual and expected deceleration rates.
If this parameter is set to 0%, the maximum stop time is
directly set in parameter 31.38. Otherwise,
maximum allowed deviation from the expected deceleration
rate, which is calculated from parameters 23.11...23.19. If the
actual deceleration rate (01.29) deviates too much from the
expected rate, the drive trips on
of
06.17 Drive status word
If
31.32
is set to 0% and
supervision is disabled.
Maximum deviation from expected deceleration rate.
If parameter
31.37 Ramp stop supervision
parameter defines the maximum time a ramp stop is allowed
to take. If the motor has not stopped when the time elapses,
the drive trips on
73B1 Stop
status word
2, and coasts to a stop.
If
31.37
is set to a value other than 0%, this parameter
defines a delay between the receipt of the stop command and
the activation of the supervision. It is recommended to specify
a short delay to allow the speed change rate to stabilize.
Maximum ramp-down time, or supervision activation delay.
Selects warnings to be suppressed. The parameter is a 16-bit
word with each bit corresponding to a warning. Whenever a
bit is set to 1, the corresponding warning is suppressed.
The bits of this binary number correspond to the following
warnings:
Warning suppression word.
Sets a custom motor current fault limit.
The drive automatically sets an internal motor current limit
according to the drive hardware. The internal limit is
appropriate in most cases, but this parameter can be used to
set a lower current limit, for example, to protect a permanent
magnet motor from demagnetization.
Note: The limit defines the maximum peak current of one
phase.
With this parameter at 0.0 A, only the internal limit is in force.
Custom motor current fault limit.
and
31.38 Ramp
01.29 Speed change
31.37
73B1 Stop
failed, sets bit 14
2, and coasts to a stop.
31.33
is set to 0 s, the ramp stop
is set to 0%, this
failed, sets bit 14 of
Parameters 311
Def/FbEq16
0%
defines the
1 = 1%
0 s
06.17 Drive
1 = 1 s
0000b
1 = 1
0.00 A
See par.
46.05