316 Parameters
No.
Name/Value
33.10
On-time 1 actual
0...4294967295 s
33.11
On-time 1 warn limit
0...4294967295 s
33.12
On-time 1 function
Bit
Function
0
Counter mode
0 = Loop: When the limit is reached, the counter is reset. The counter status (bit 0 of
33.01) switches to 1 for one second. The warning (if enabled) stays active for at least 10
seconds.
1 = Saturate: When the limit is reached, the counter status (bit 0 of 33.01) switches to 1,
and remains so until
is reset.
1
Warning enable
0 = Disable: No warning is given when the limit is reached
1 = Enable: A warning (see 33.14) is given when the limit is reached
2...15
Reserved
0000b...0011b
33.13
On-time 1 source
False
True
RO1
Other [bit]
33.14
On-time 1 warn
message
On-time 1
exceeded
Clean device
Maintain additional
cooling fan
Maintain cabinet
fan
Maintain DC
capacitors
Maintain motor
bearing
Description
Displays the actual present value of on-time timer 1.
The timer runs whenever the signal selected by parameter
33.13 On-time 1 source
When the timer exceeds the limit set by
limit, bit 0 of
33.01 Counter status
specified by
33.14 On-time 1 warn message
enabled by
33.12 On-time 1
The timer can be reset from the Drive composer PC tool, or
from the control panel by keeping Reset depressed for over 3
seconds.
Actual present value of on-time timer 1.
Sets the warning limit for on-time timer 1.
Warning limit for on-time timer 1.
Configures on-time timer 1.
33.10
is reset. The warning (if enabled) also stays active until
On-time timer 1 configuration word.
Selects the signal to be monitored by on-time timer 1.
Constant 0 (timer disabled).
Constant 1.
Bit 0 of
10.21 RO status
Source selection (see
Terms and abbreviations
Selects the optional warning message for on-time timer 1.
A886 On-time
1. The message text can be edited on the
control panel by choosing Menu – Settings – Edit texts.
A88C Device
clean.
A890 Additional
cooling.
A88E Cabinet
fan.
A88D DC
capacitor.
A880 Motor
bearing.
is on.
33.11 On-time 1 warn
is set to 1. The warning
is also given if
function.
(page 188).
on page 148). -
Def/FbEq16
-
-
0 s
-
0000b
33.10
1 = 1
False
0
1
2
On-time 1
exceeded
0
6
7
8
9
10