ABB +N5600 Firmware Instructions page 327

Single drive
Table of Contents

Advertisement

No.
Name/Value
35.21
Temperature 2
source
Disabled
Estimated
temperature
KTY84 analog I/O
KTY84 encoder
module 1
KTY84 encoder
module 2
1 × Pt100 analog
I/O
2 × Pt100 analog
I/O
3 × Pt100 analog
I/O
Description
Selects the source from which measured temperature 2 is
read.
For wiring examples, see the hardware manual of the drive.
Usually this source is from a sensor connected to the motor
controlled by the drive, but it could be used to measure and
monitor a temperature from other parts of the process as long
as a suitable sensor is used as per the selection list.
None. Temperature monitoring function 2 is disabled.
Estimated motor temperature (see parameter
estimated
temperature).
The temperature is estimated from an internal drive
calculation. It is important to set up the ambient temperature
of the motor in
35.50 Motor ambient
KTY84 sensor connected to the analog input selected by
parameter
35.24 Temperature 2 AI source
output. The input and output can be on the drive control unit
or on an extension module.
The following settings are required:
• Set the hardware jumper or switch related to the analog
input to U (voltage). Any change must be validated by a
control unit reboot.
• Set the unit selection parameter of the input to volt.
• Set the source selection parameter of the analog output to
"Force KTY84
excitation".
• Select the analog input in parameter 35.24. In case the
input is located on an I/O extension module, use the
selection
Other
to point at the actual input value parameter
(for example,
14.26 AI1 actual
The analog output feeds a constant current through the
sensor. As the resistance of the sensor changes along with its
temperature, the voltage over the sensor changes. The
voltage is read by the analog input and converted into
degrees.
KTY84 sensor connected to encoder interface 1.
See also parameters
91.21 Module 1 temp sensor type
91.22 Module 1 temp filter
KTY84 sensor connected to encoder interface 2.
See also parameters
91.24 Module 2 temp sensor type
91.25 Module 2 temp filter
Pt100 sensor connected to a standard analog input selected
by parameter
35.24 Temperature 2 AI source
output. The input and output can be on the drive control unit
or on an extension module.
The required settings are the same as with selection
analog
I/O, except that the source selection parameter of the
analog output must be set to
As selection
1 × Pt100 analog
connected in series. Using multiple sensors improves
measurement accuracy significantly.
As selection
1 × Pt100 analog
connected in series. Using multiple sensors improves
measurement accuracy significantly.
35.01 Motor
temperature.
and an analog
value).
time.
time.
and an analog
Force Pt100
excitation.
I/O, but with two sensors
I/O, but with three sensors
Parameters 327
Def/FbEq16
Disabled
0
1
2
3
and
4
and
5
KTY84
6
7