ABB +N5600 Firmware Instructions page 313

Single drive
Table of Contents

Advertisement

No.
Name/Value
32.06
Supervision 1
action
No action
Warning
Fault
Fault if running
32.07
Supervision 1
signal
Zero
Speed
Frequency
Current
Torque
DC voltage
Output power
AI1
AI2
Speed ref ramp in
Speed ref ramp out
Speed ref used
Torque ref used
Freq ref used
Process PID output
Process PID
feedback
Other
32.08
Supervision 1 filter
time
0.000 ... 30.000 s
32.09
Supervision 1 low
-21474830.00 ...
21474830.00
32.10
Supervision 1 high
-21474830.00 ...
21474830.00
32.15
Supervision 2
function
Disabled
Low
Description
Selects the action the drive takes when the value monitored
by signal supervision 1 exceeds its limits.
Note: This parameter does not affect the status indicated by
32.01 Supervision
status.
No action taken.
A warning
(A8B0 Signal
The drive trips on
80B0 Signal
If running, the drive trips on
Selects the signal to be monitored by signal supervision
function 1.
None.
01.01 Motor speed used
01.06 Output frequency
01.07 Motor current
(page 152).
01.10 Motor torque
(page 152).
01.11 DC voltage
(page 152).
01.14 Output power
(page 153).
12.11 AI1 actual value
(page 197).
12.21 AI2 actual value
(page 199).
23.01 Speed ref ramp input
23.02 Speed ref ramp output
24.01 Used speed reference
26.02 Torque reference used
28.02 Frequency ref ramp output
40.01 Process PID output actual
40.02 Process PID feedback actual
Source selection (see
Terms and abbreviations
Defines a filter time constant for the signal monitored by
signal supervision 1.
Signal filter time.
Defines the lower limit for signal supervision 1.
Low limit.
Defines the upper limit for signal supervision 1.
Upper limit.
Selects the mode of signal supervision function 2. Determines
how the monitored signal (see parameter 32.17) is compared
to its lower and upper limits
The action to be taken when the condition is fulfilled is
selected by 32.16.
Signal supervision 2 not in use.
Action is taken whenever the signal falls below its lower limit.
supervision) is generated.
supervision.
80B0 Signal
supervision.
(page 152).
(page 152).
(page 257).
(page 257).
(page 263).
(page 279).
(page 285).
(page 341).
(page 341).
on page 148). -
(32.19
and
32.20
respectively).
Parameters 313
Def/FbEq16
No action
0
1
2
3
Zero
0
1
3
4
6
7
8
9
10
18
19
20
21
22
24
25
0.000 s
1000 = 1 s
0.00
-
0.00
-
Disabled
0
1