Fujitsu M10 Installation Manual page 149

Hide thumbs Also See for M10:
Table of Contents

Advertisement

Figure 3-83     Securing the PCI expansion unit
A A
10. Attach the cable support.
For the Type-1 cable support
a. From the inside of the cable support fixing bracket, align the two screws in the
right cable support bracket with the circular holes at the front of the groove,
and attach the screws (A in
b. Slide the cable support bracket toward the chassis while holding the latch (B in
Figure
3-84) attached to it.
c. Attach the left cable support bracket in the same manner. At this time, the left
and right sides should have been slid the same amount (depth) toward the
chassis.
d. Secure the cable support with two M3 screws (C in
e. Close the rear door of the rack, and confirm that the cable support brackets do
not interfere. If they interfere, slide the cable support toward the chassis while
holding the latches (B in
brackets. The cable support should be in the position nearest the chassis, with
the cable support bracket latches engaged.
f. If the cable support interferes with the door even when you slide it toward the
chassis as far as possible, remove the cable support.
A
Figure
3-84).
Figure
3-84) of the left and right cable support
Chapter 3 Installing the System
Figure
3-84).
135