Checking Environmental Conditions - Fujitsu M10 Installation Manual

Hide thumbs Also See for M10:
Table of Contents

Advertisement

2.5

Checking Environmental Conditions

This section describes the environmental conditions for the SPARC M10 systems. The
server can be installed at locations that meet the environmental conditions listed in
Table
Note - When designing environmental control systems such as air conditioning facilities,
confirm that the air taken in by each chassis meets the requirements specified in this section.
The environmental conditions described in
chassis. The optimal conditions represent the recommended environment in
operation. The component failure rate may increase substantially when the system
operates for prolonged periods in an environment that is at or close to the operation-
time (in operation) limit values, or when the system is installed in an environment
that is at or close to the non-operation-time (not in operation) limit values. To
minimize the occurrence of system downtime due to a component failure, set the
temperature and humidity within the optimal condition range.
 
The following conditions must be met to prevent overheating:
Neither warm air nor hot air blows directly on the front of the rack
Neither warm air nor hot air blows directly on the front panel of any chassis
Table 2-5     Environmental conditions
Item
Ambient
temperature
Relative
humidity
(*1)
Maximum
wet-bulb
temperature
Altitude limit
(*3)
Fujitsu M10/SPARC M10 Systems Installation Guide ・ July 2015
38
2-5.
In operation
5°C to 35°C
41°F to 95°F
- When installed in server room
20% RH to 80% RH
- When installed in office (*2)
20% RH to 80% RH
- When installed in server room
26°C (78.8°F)
- When installed in office (*2)
29°C (84.2°F)
0 m to 3,000 m
(0 ft. to 10,000 ft.)
Table 2-5
reflect test results from each
Not in operation
- When unpacked
0℃ to 50℃
(32℉ to 122℉ )
- When still packed
-25℃ to 60℃
(-4℉ to 140℉ )
- When installed in
server room
8% RH to 80% RH
- When installed in
office (*2)
8% RH to 80% RH
- When installed in
server room
27 ℃ (80.6 ℉ )
- When installed in
office (*2)
29°C (84.2°F)
0 m to 12,000 m
(0 ft. to 40,000 ft.)
Optimal
condition
21°C to
23°C
70°F to
74°F