232
Parameter
Alternative
settings
51.29 FILE
xyz (binary coded
CONFIG ID*
decimal)
51.30 FILE
xyz (binary coded
CONFIG REV*
decimal)
51.31 FBA
(0) IDLE
STATUS*
(1) EXEC. INIT
(2) TIME OUT
(3) CONFIG
ERROR
(4) OFF-LINE
(5) ON-LINE
(6) RESET
51.32 FBA CPI FW
REV*
51.33 FBA APPL
FW REV*
*Parameters 51.27 to 51.33 are only visible when type Rxxx fieldbus adapter is installed.
After the module configuration parameters in group 51 have been set, the drive
control parameters (section
and adjusted where necessary.
The new settings will take effect when the drive is next powered up, or when
parameter 51.27 is activated.
Fieldbus control
Setting for
fieldbus control
Drive control parameters
Function/Information
Displays the fieldbus adapter module configuration
file identification stored in the memory of the drive.
This information is drive application program-
dependent.
Displays the fieldbus adapter module configuration
file revision stored in the memory of the drive.
x = major revision number; y = minor revision
number; z = correction number. Example: 1 =
revision 0.01.
Displays the status of the adapter module.
IDLE = Adapter not configured.
EXEC. INIT = Adapter initialising.
TIME OUT = A timeout has occurred in the
communication between the adapter and the drive.
CONFIG ERROR = Adapter configuration error.
The major or minor revision code of the CPI
program revision in the drive is not the revision
required by the module (refer to par. 51.32) or
configuration file upload has failed more than five
times.
OFF-LINE = Adapter is off-line.
ON-LINE = Adapter is on-line.
RESET = Adapter performing a hardware reset.
Displays the CPI program revision of the module
inserted in slot 1. x = major revision number;
y = minor revision number; z = correction number.
Example: 107 = revision 1.07.
Displays the application program revision of the
module inserted in slot 1. x = major revision
number; y = minor revision number; z = correction
number. Example: 107 = revision 1.07.
on page 237) must be checked