Fieldbus reference scaling

With the Generic Drive communication profile active, the speed reference value
received from the fieldbus and the actual speed value received from the drive are
scaled as shown in the table below.
Note: Any correction of the reference (see section
applied before scaling.
Ref.
Application
No.
Macro used
(par. 99.02)
REF1
(any)
REF2
Crane macro
with speed
mode
Crane macro
with M/F in
torque mode
* With DTC the filter time of the actual speed value can be adjusted using parameter 34.04.
** Note: The maximum reference value is 163% (that is,163% = 1.63 · value of parameter 99.08/99.07 value).
Range
Reference
type
-32768...
Speed or
32767
Frequency
-32768...
Speed or Freq.
32767
(not with
FAST COMM)
Speed or Freq.
with
FAST COMM
-32768...
Torque
32767
(not with
FAST COMM)
Torque with
FAST COMM
References
Speed reference
scaling
0 = 0
20000 =
[par. 99.08 (DTC) /
99.07 (scalar)]**
-20000 = -[par. 11.08]
-1 = -[par. 11.07]
0 = [par. 11.07]
20000 = [par. 11.08]
-20000 = -[par. 11.08]
0 = 0
20000 = [par. 11.08]
-10000 = -[par. 11.08]
-1 = -[par. 11.07]
0 = [par. 11.07]
10000 = [par. 11.08]
-10000 = -[par. 11.08]
0 = 0
10000 = [par. 11.08]
on page 242) is
Actual speed
Notes
scaling*
0 = 0
20000 = [par.
99.08 (DTC) /
99.07 (scalar)]**
0 = 0
Final reference
limited with
20000 = [par.
20.01/20.02
99.08 (DTC) /
[speed] or
99.07 (scalar)]**
20.07/20.08
[frequency]
0 = 0
Final reference
limited with
20000 = [par.
20.01/20.02
99.08 (DTC) /
[speed] or
99.07 (scalar)]**
20.07/20.08
[frequency]
0 = 0
Final reference
limited with 20.04
20000 = [par.
99.08 (DTC) /
99.07 (scalar)]**
0 = 0
Final reference
limited with 20.04
20000 = [par.
99.08 (DTC) /
99.07 (scalar)]**
Fieldbus control
259