ABB ACS800 Firmware Manual page 292

Crane control program
Hide thumbs Also See for ACS800:
Table of Contents

Advertisement

292
FAULT
CAUSE
INV OVERTEMP
Converter module temperature is excessive.
(4290)
3.17 FW 5 bit 13
I/O COMM ERR
Communication error on control board,
channel CH1
(7000)
Electromagnetic interference
3.06 FW 2 bit 6
LINE CONV
Fault on line side converter
(FF51)
MOTOROVER
The speed exceeds the MOT OVERSPEED
SPD
LEV (Par. 74.01)
(FFF0)
3.33 CRANE FW bit 0
MOTOR PHASE
One of motor phases is lost due to fault in
motor, motor cable, thermal relay (if used) or
(FF56)
internal fault.
3.06 FW 2 bit 15
(programmable
Fault Function
30.16)
MOTOR TEMP
Motor temperature is too high (or appears to be
too high) due to excessive load, insufficient
(4310)
motor power, inadequate cooling or incorrect
3.05 FW 1 bit 6
start-up data.
(programmable
Fault Function
30.04
... 30.09)
Fault tracing
WHAT TO DO
Check ambient temperature. If it exceeds
40°C, ensure that load current does not
exceed derated load capacity of drive. See
appropriate hardware manual.
Check that ambient temperature setting is
correct (parameter 95.10).
Check converter module cooling air flow and
fan operation.
Cabinet installation: Check cabinet air inlet
filters. Change when necessary. See
appropriate hardware manual.
Modules installed in cabinet by user: Check
that cooling air circulation in cabinet has been
prevented with air baffles. See module
installation instructions.
Check inside of cabinet and heatsink of
converter module for dust pick-up. Clean when
necessary.
Reset and restart after problem is solved and
let converter module cool down.
Check connections of fibre optic cables on
channel CH1.
Check all I/O modules (if present) connected to
channel CH1.
Check for proper earthing of equipment. Check
for highly emissive components nearby.
Shift panel from motor side converter control
board to line side converter control board.
See line side converter manual for fault
description.
Check Torque and Current limit settings
Check motor and motor cables
Check pulse encoder connections if used
Check motor and motor cable.
Check thermal relay (if used).
Check Fault Function parameters. Disable this
protection.
Check motor ratings and load.
Check start-up data.
Check Fault Function parameters.