Start-Up Data - ABB ACS800 Firmware Manual

Crane control program
Hide thumbs Also See for ACS800:
Table of Contents

Advertisement

224
Index
Name/Selection
98.13
AI/O EXT AI1 FUNC
UNIPOLAR AI5
BIPOLAR AI5
98.14
AI/O EXT AI2 FUNC
UNIPOLAR AI6
BIPOLAR AI6
98.16
SIN FILT SUPERV
NO
RDIO-SLOT1
RDIO-SLOT2
RDIO-DDCS

99 START-UP DATA

99.01
LANGUAGE
ENGLISH
ENGLISH AM
DEUTSCH
ITALIANO
ESPANOL
PORTUGUES
NEDERLANDS
FRANCAIS
DANSK
SUOMI
SVENSKA
CESKY
POLSKI/LOC1
PO-RUS/LOC2
Actual signals and parameters
Description
Defines the signal type for input 1 of the analogue I/O extension module (AI5 in
the drive application program). The setting must match the signal connected to
the module.
Note: The communication must be activated with parameter 98.06.
Unipolar
Bipolar
Defines the signal type for input 2 of the analogue I/O extension module (AI6 in
the drive application program). The setting must match the signal connected to
the module.
Note: The communication must be activated with parameter 98.06.
Unipolar
Bipolar
Activates the communication to the digital I/O extension module and reserves
the module for the use of the sine-filter temperature measurement.
Parameter is visible if parameter
value is automatically set to NO, when parameter 95.04 value is changed.
Note: This parameter is used only in special applications.
Supervision disabled.
Module type: RDIO. Connection interface: Option slot 1 of the drive.
Module type: RDIO. Connection interface: Option slot 2 of the drive.
Module type: RDIO. Connection interface: Optional I/O module adapter (AIMA)
that communicates with the drive through a fibre optic DDCS link.
Note: Module node number must be set to 8. For directions, see RDIO Module
User's Manual [3AFE64485733 (English)].
Language selection. Definition of motor set-up data. This group gets write
protect locked once the motor data is entered and the drive is initialized. The
lock can be opened with passcode 584.
Selects the display language.
British English
American English. If selected, the unit of power used is HP instead of kW.
German
Italian
Spanish
Portuguese
Dutch
French
Danish
Finnish
Swedish
Czech
Polish
Russian
98.04
is set to SIN or EX&SIN. Parameter
FbEq
1
2
1
2
1
2
3
4
0
1
2
3
4
5
6
7
8
9
10
11
12
13