Scaling Actual Encoder Position Signal (Mm) To Analogue Output As Ma - ABB ACS800 Firmware Manual

Crane control program
Hide thumbs Also See for ACS800:
Table of Contents

Advertisement

310

Scaling actual encoder position signal (mm) to analogue output as mA

The actual encoder position signal
4 ... 20 mA for analogue outputs and sent to other systems as an mA signal, for
example, for supervision or protection purposes. For more information on the
Position function, see section
Create an AP file for scaling the actual encoder position signal to an analogue output
according to the following example. In the example:
• 4 mA is the negative position
• 12 mA is the zero position
• 20 mA is the positive position.
Adaptive Programming examples for crane control
02.21
POS ACT PPU (mm) can be scaled to
Position
on page 91.