238
Parameter
Setting for
fieldbus control
SYSTEM CONTROL INPUTS
16.01
COMM.CW
16.04
COMM.CW
16.07
DONE; SAVE
COMMUNICATION FAULT FUNCTIONS
30.18
FAULT
NO
30.19
0.1 ... 60.0 s
30.21
0.0 ... 60.0 s
FIELDBUS REFERENCE TARGET SELECTION
90.01
0 ... 8999
90.02
0 ... 8999
90.03
0 ... 8999
90.04
0 ... 8999
90.05
0 ... 8999
Fieldbus control
Function/Information
Enables the control of the Run Enable signal through fieldbus 03.01 Main
Control Word bit 3.
Note: Must be set to YES when the Generic Drive communication profile is
selected (see Par. 98.07).
Enables fault reset through fieldbus 03.01 Main Control Word bit 7.
Note: Reset through fieldbus Control Word (03.01 bit 7) is enabled
automatically and it is independent of parameter
10.01
or
10.02
is set to COMM.CW.
Saves parameter value changes (including those made through fieldbus
control) to permanent memory.
Determines drive action in case fieldbus communication is lost.
Note: The communication loss detection is based on monitoring of
received Main and Auxiliary data sets (whose sources are selected with
parameters 90.04 and 90.05 respectively).
Defines the time between Main Reference data set loss detection and the
action selected with parameter 30.18.
Defines the time between Auxiliary Reference data set loss detection and
the action selected with parameter 30.18.
Note: This supervision function is disabled if this parameter, or parameters
90.01, 90.02 and 90.03 are set to 0.
Defines the drive parameter into which the value of fieldbus reference
REF3 is written.
Format: xxyy, where xx = parameter group (10 to 89), yy = parameter
Index. For example, 3001 = parameter 30.01.
Defines the drive parameter into which the value of fieldbus reference
REF4 is written.
Format: see parameter 90.01.
Defines the drive parameter into which the value of fieldbus reference
REF5 is written.
Format: see parameter 90.01.
Defines the drive parameter into which the value of fieldbus reference
REF6 is written.
Format: see parameter 90.01.
Defines the drive parameter into which the value of fieldbus reference
REF7 is written.
Format: see parameter 90.01.
16.04
setting if parameter