Start-up and control through the I/O interface

Chapter overview

The chapter instructs how to:
• do the start-up
• start, stop, change the direction of rotation, and adjust the speed of the motor
through the I/O interface
• perform an identification run for the drive.

How to start-up the drive

You can perform a limited start-up. The drive gives no guidance: go through the very
basic settings by following the instructions given in the manual.
• If you want to perform the limited start-up, follow the instructions given in
section
page 18.
Note! Start the drive in the following order:
• First, select values for parameter group 99, that is, enter the motor data and
create the DTC motor model.
• Only then, give values for parameter groups 10...98, that is, adjust the application
parameters AFTER the DTC motor model is ready. Never give parameter groups
10...98 without having filled in parameter group 99 first.
Note: Once the ID run has been completed successfully, group 99 is locked to
prevent resetting the ID run results. The group can be reopened, if required, by
entering pass code 584 into parameter
How to perform the limited start-up (covers only the basic settings)
16.03
PASS CODE.