68
Flux optimisation
Flux optimisation reduces the total energy consumption and motor noise level when
the drive operates below the nominal load. The total efficiency (motor and the drive)
can be improved by 1% to 10%, depending on the load torque and speed.
Settings
Parameter 26.01.
FS method
The Flux stabilization method improves the behaviour of open-loop trolley drives and
long travel drives without speed feedback especially when the drive operates around
the zero speed with high load. The method is active on frequencies below 10% of
nominal frequency and when the torque exceeds 30%.
Settings
Parameter 26.07.
Program features