WARNING
CAUSE
MOT POW LIM
Drive limits motor power according to limits
defined with parameters
(FF86)
3.18 AW 5 bit 12
(programmable
Fault Function
30.23)
MOT TORQ LIM
Drive limits motor torque according to
calculated motor pull-out torque limit and
(FF85)
minimum and maximum torque limits defined
3.18 AW 5 bit 11
with parameters
(programmable
Fault Function
30.23)
PANEL LOSS
Control panel selected as active control
location for drive has ceased communicating.
(5300)
3.09 AW 2 bit 13
(programmable
Fault Function
30.02)
POINTER ERROR
Source selection (pointer) parameter points to
non existing parameter index.
(FFD0)
->POWEROFF!
Inverter type (for example, sr0025_3) has been
changed. Inverter type is usually changed at
(FF39)
factory or during drive implementation.
PP OVERLOAD
Excessive IGBT junction to case temperature.
This can be caused by excessive load at low
(5482)
frequencies (for example, fast direction change
3.18 AW 5 bit 5
with excessive load and inertia).
REPLACE FAN
Running time of inverter cooling fan has
exceeded its estimated life time.
(4280)
3.18 AW 5 bit 0
SLOW DOWN UP
Slowdown signal
direction
(FFF4)
SLOW DOWN
Slowdown signal
DOWN
direction
(FFF5)
START INHIBI
Optional start inhibit hardware logic is
activated.
(FF7A)
AW 1 bit 0
20.11
and 20.12.
20.13
and 20.14.
10.09
activated in the Up
10.09
activated in the down
WHAT TO DO
Informative alarm
Check parameter
20.11
P MOTORING LIM
and
20.12
P GENERATING LIM settings.
Check Fault Function parameters.
Informative alarm
Check parameter
20.13
MIN TORQ SEL and
20.14
MAX TORQ SEL settings.
Check Fault Function parameters.
If LIMIT WORD 1 bit 0 TORQ MOTOR LIM
is 1,
- check motor parameter settings (parameter
group
99 START-UP
DATA)
- ensure that ID run has been completed
successfully.
Check panel connection (see appropriate
hardware manual).
Check control panel connector.
Replace control panel in mounting platform.
Check Fault Function parameters.
Check source selection (pointer) parameter
settings.
Switch control board power off to validate
inverter type change.
Increase ramp time.
Reduce load.
Replace fan.
Reset fan run time counter 01.44.
Run the motor in the opposite direction and
deactivate the Slowdown signal. Or let the
drive run in the limited speed reference.
Run the motor in the opposite direction and
deactivate the Slowdown signal. Or let the
drive run in the limited speed reference.
Check start inhibit circuit (AGPS board).
285
Fault tracing