【#2221】 SV021 OLT Overload detection time constant
Normally, set to "60". (For machine tool builder adjustment.)
Related parameters: SV022
---Setting range---
1 to 999 (s)
【#2222】 SV022 OLL Overload detection level
Set the "Overload 1" (Alarm 50) current detection level as percentage to the stall current.
Normally set this parameter to "150". (For machine tool builder adjustment.)
Related parameters: SV021
---Setting range---
110 to 500 (Stall current %)
【#2223】 SV023 OD1 Excessive error detection width during servo ON
Set the excessive error detection width in servo ON.
When set to "0", the excessive error alarm detection will be ignored, so do not set to "0".
<Standard setting value>
OD1=OD2= (Rapid traverse rate [mm/min]) / (60×PGN1) / 2 [mm]
Related parameters: SV026
---Setting range---
0 to 32767 (mm)
However, when SV084/bitC=1, the setting range is from 0 to 32767 (μm).
【#2224】 SV024 INP In-position detection width
Set the in-position detection width.
Set the positioning accuracy required for the machine.
The lower the setting is, the higher the positioning accuracy will be. However the cycle time (settling
time) becomes longer.
The standard setting value is "50".
---Setting range---
0 to 32767 (μm)
C70 Setup Manual
Appendix 1.5 Servo Parameters