A01 MULTI CPU ERROR 2112
Details
- The module other than intelligent function module is specified by the intelligent function module/
special function module dedicated instruction. Or, it is not the corresponding intelligent function
module.
- There is no network No. specified by the network dedicated instruction. Or the relay target network
does not exist.
Remedy
- Read the individual information of the error using a programming tool and check the special function
module dedicated instruction (network instruction) that corresponds to the value (program error part)
to make modification.
A01 MULTI CPU ERROR 2116
Details
- An instruction that does not allow the module under the control of another CPU to be specified is
being used for a similar task.
Remedy
- Read the individual information of the error using a programming tool and check the special function
module dedicated instruction (network instruction) that corresponds to the value (program error part)
to make modification.
A01 MULTI CPU ERROR 2124
Details
- A module is installed to the 65th or higher slot.
- A module is installed to the slot whose number is greater than the number of slots specified in the
base setting.
- A module is installed to the location corresponding to the I/O points of the 4,096 or greater.
- A module is installed to the slot whose assigned I/O range includes the limit of.
Remedy
- Remove the module installed to the 65th or later slot.
- Remove the module installed at the slot whose number is greater than the number of slots specified
in the base setting.
- Remove the module installed to the location of I/O points, 4,096 or greater.
- Replace the last module to a module which does not exceed the 4,096th point.
A01 MULTI CPU ERROR 2125
Details
- A module which the QCPU cannot recognize has been installed.
- There was no response form the intelligent function module/special function module.
Remedy
- Install a usable module.
- The intelligent function module is experiencing a hardware fault. Contact your local service center.
A01 MULTI CPU ERROR 2140
Details
- Motion CPU (Q172LX, Q172EX (-S1, S2, S3) or Q173PX(-S1)) is mounted to the CPU slot or slot
No. 0 to 2.(QnUD(H)CPU does not lead this error.)
Remedy
- Remove the motion CPU that is mounted to the CPU slot or slot No. 0 to 2.
A01 MULTI CPU ERROR 2150
Details
- In a multiple CPU system, the control CPU of the intelligent function module incompatible with the
multiple CPU system is set to other than CPU No.1.
Remedy
- Change the intelligent function module for the one compatible with the multiple CPU system (function
version B or later).
- Change the setting of the control CPU of the intelligent function module incompatible with the
multiple CPU system to CPU No.1.