L12 DN LINK ERROR 81 (Error-detected slave node No. )
Details
A deviceNet initialization error has occurred. The error-detected node No. is other than FFH and FEH.
- A connection other than explicit messages and polling was allocated.
"Error-detected slave node No." shows the error-detected slave node No. in decimal.
Remedy
- Do not allocate I/O connections other than polling.
L12 DN LINK ERROR 82 (Error-detected slave node No. )
Details
A deviceNet initialization error has occurred. The error-detected node No. is other than FFH and FEH.
- The number of reception bytes of polling is greater than the maximum number of reception points.
"Error-detected slave node No." shows the error-detected slave node No. in decimal.
Remedy
- Match the I/O point setting of the master node with that of the QJ71DN91.
L13 DN MESSAGE ERR. 161
Details
A message communication execution error has occurred.
- The specified slave node No. is other than 0 to 63.
Remedy
- Set it between 0 and 63.
C70 Setup Manual
Appendix 2.12 Network Errors (L)