2.10.5 Connection of the high power factor converter (FR-
HC2)
When connecting the high power factor converter (FR-HC2) to suppress power harmonics, perform wiring securely as follows.
Incorrect connection will damage the high power factor converter and the inverter.
After making sure that the wiring is correct and secure, set the rated motor voltage in Pr.19 Base frequency voltage (under
V/F control) or Pr.83 Rated motor voltage (under other than V/F control) and "2" in Pr.30 Regenerative function selection.
(Refer to
page
689.)
MCCB
Three-phase
AC power
supply
*1
Remove jumpers across terminals R/L1 and R1/L11 as well as across terminals S/L2 and S1/L21, and connect the power supply for the control
circuit to terminals R1/L11 and S1/L21. Do not connect anything to power input terminals (R/L1, S/L2, and T/L3). Incorrect connection will damage
the inverter. (The E.OPT fault (option fault) occurs. (Refer to
*2
Do not install an MCCB across terminals P/+ and N/- (between terminals P and P/+ or between terminals N and N/-). Connecting the opposite
polarity of terminals N/- and P/+ will damage the inverter.
*3
Use Pr.178 to Pr.189 (Input terminal function selection) to assign the terminals used for the X10 (X11) signal. (Refer to
For RS-485 or any other communication where the start command is only transmitted once, use the X11 signal to save the operation mode at the
time of an instantaneous power failure.
*4
Assign the IPF signal to a terminal on the FR-HC2. (Refer to the Instruction Manual of the FR-HC2.)
*5
Always connect terminal RDY on the FR-HC2 to a terminal where the X10 signal or MRS signal is assigned on the inverter. Always connect
terminal SE on the FR-HC2 to terminal SD on the inverter. Not connecting these terminals may damage the FR-HC2.
*6
Always connect terminals R/L1, S/L2, and T/L3 on the FR-HC2 to the power supply. Operating the inverter without connecting them will damage
the FR-HC2.
*7
Do not install an MCCB or MC across terminals (R/L1, S/L2, T/L3) on the reactor 1 and terminals (R4/L14, S4/L24, T4/L34) on the FR-HC2. Doing
so disrupts proper operation.
*8
Securely perform grounding (earthing) by using the grounding (earthing) terminal.
*9
Installation of a fuse is recommended. (Refer to the Instruction Manual of the FR-HC2.)
*10 Outside box is not available for the FR-HC2-H280K or higher. Connect filter capacitors, inrush current limit resistors, and magnetic contactors.
(Refer to the Instruction Manual of the FR-HC2.)
NOTE
• The voltage phases of terminals R/L1, S/L2, and T/L3 and the voltage phases of terminals R4/L14, S4/L24, and T4/L34 must
be matched.
• The control logic (sink logic/source logic) of the high power factor converter and the inverter must be matched. (Refer to
72.)
• Do not connect a DC reactor (FR-HEL) to the inverter when the FR-HC2 is connected.
2.10.6 Connection of the power regeneration common
converter (FR-CV)
When wiring for connecting the power regeneration common converter (FR-CV) to the inverter, make sure to match the terminal
symbols (P/+, N/-) on the inverter and on the power regeneration common converter.
The FR-CV is compatible with the FR-A820-03160(55K) or lower and the FR-A840-01800(55K) or lower.
Outside box
Reactor1
(FR-HCB2)
(FR-HCL21)
MC
∗7
∗7
R2/
R/
R2/
L12
L1
L12
S/
S2/
S2/
L2
L22
L22
T2/
T/
T2/
L3
L32
L32
∗8
∗8
High power
factor converter
Reactor2
∗10
(FR-HC2)
(FR-HCL22)
∗7
R3/
∗7
R3/
R4/
R4/L14
L13
L13
L14
S3/
S4/
S3/
S4/L24
L23
L23
L24
T3/
T3/
T4/
T4/L34
L33
L33
L34
∗8
P/+
ROH1
ROH
N/-
ROH2
SD
RDY
88R
88R
∗4
IPF
88S
88S
R/L1
RSO
S/L2
∗6
SE
T/L3
R1/L11
S1/L21
∗8
page
757.))
2.10 Connection of stand-alone option units
Inverter
∗1
Motor
R/L1
U
S/L2
V
M
T/L3
W
R1/L11
S1/L21
Earth
∗9
Fuse
(ground)
P/+
∗2
N/-
∗5
∗3
X10
X11
∗3
RES
SD
∗8
page
496.)
2. INSTALLATION AND WIRING
1
2
3
4
5
6
7
8
9
10
page
103

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-a820-00167 (2.2k)Fr-a820-00046-gf (0.4k)Fr-a820-00250 (3.7k)Fr-a820-00105-gf (1.5k)Fr-a820-00077 (0.75k)Fr-a820-00250-gf (3.7k) ... Show all

Table of Contents