Deviation
Pr.577 - 1000%
Output frequency
Pr.576
RUN
PID
SLEEP
*1
When the PID output shutoff release level is reached during a deceleration stop, output shutoff is released, operation is re-accelerated and PID
control is continued. During deceleration, Pr.576 Output interruption detection level is invalid.
 Integral stop selection when the frequency is limited (Pr.1015)
• The operation for the integral term can be selected when the frequency or the manipulated amount is limited during PID
control. The operation during output suspension can be selected for the integral term using the PID output suspension
(sleep) function.
• The manipulation range can be selected.
Operation at limited
Pr.1015 setting
0 (initial value)
Integral stop
1
Integral continuation
2
Integral stop
10
Integral stop
11
Integral continuation
12
Integral stop
NOTE
• While the integral stop is selected, the integral stop is enabled when any of the following conditions is met.
• The frequency reaches the upper or lower limit.
• The manipulated amount reaches plus or minus 100% (Pr.1015 = "0 or 10").
• The manipulated amount reaches 0% or 100% (Pr.1015 = "2 or 12").
 PID monitor function
• This function displays the PID control set point, measured value and deviation on the operation panel, and can output these
from the terminals FM/CA and AM.
• An integral value indicating a negative % can be displayed on the deviation monitor. 0% is displayed as 1000. (These
values cannot be output on the deviation monitor from terminals FM and CA.)
When Pr.554="10 to 13", reverse operation (Pr.128="10")
Less than Pr.575
Pr.575 or more
Range of manipulation
frequency
-100% to +100%
0 to 100%
-100% to +100%
0 to 100%
Integral stop conditions
∗1
Deceleration stop
SLEEP period
OFF
ON
Operation during output
interruption
Integral clear
Integral stop
Cancel
level
Time
5. PARAMETERS