 Selection of control source in Network operation mode (Pr.338, Pr.339)
• There are two control sources: the start command source, which controls the signals related to the inverter stand command
and function selection, and the speed command source, which controls signals related to frequency setting.
• The following table shows the commands given via the external terminals or given through communication (via the RS-485
terminals or the communication option) in the Network operation mode.
Pr.338 Communication operation command
Operation
location
Pr.339 Communication speed command
selection
Running frequency command given through
Fixed
communication
function
Terminal 2
(terminal-
equivalent
Terminal 4
function)
Terminal 1
0
RL
1
RM
2
RH
3
RT
4
AU
5
JOG
6
CS
7
OH
8
REX
9
X9
10
X10
11
X11
12
X12
13
X13
14
X14
15
BRI
16
X16
17
X17
18
X18
19
X19
20
X20
22
X22
23
LX
24
MRS
STP
25
(STOP)
26
MC
27
TL
28
X28
37
X37
42
X42
43
X43
384
5. PARAMETERS
5.9 (D) Operation command and frequency command
source
source
Low-speed operation command/Remote
setting (setting clear)/Stop-on-contact
selection 0
Middle-speed operation command/
Remote setting (deceleration)
High-speed operation command/
Remote setting (acceleration)
Second function selection/ Stop-on-
contact selection 1
Terminal 4 input selection
Jog operation selection
Selection of automatic restart after
instantaneous power failure / flying start
External thermal relay input
15-speed selection
Third function selection
Inverter run enable
FR-HC2/FR-CC2 connection,
instantaneous power failure detection
PU operation external interlock
External DC injection brake operation
start
PID control valid
Brake opening completion
PU/External operation switchover
Load pattern selection forward/reverse
rotation boost
V/F switchover
Load torque high-speed frequency
S-pattern acceleration/deceleration C
switchover
Orientation command
Pre-excitation/servo ON
Output stop
PU operation interlock
Start self-holding selection
Control mode switchover
Torque limit selection
Start-time tuning start external input
Traverse function selection
Torque bias selection 1
Torque bias selection 2
0: NET
0:
1:
2:
0:
NET
EXT
EXT
NET
NET
NET
NET
EXT
EXT
Compensation
NET
External
NET
NET
External
NET
NET
External
NET
NET
External
Combined
External
External
External
NET
External
NET
NET
External
External
External
External
NET
External
NET
External
NET
NET
External
External
NET
External
NET
External
NET
External
NET
External
NET
External
NET
External
Combined
External
External
External
NET
External
NET
External
NET
External
NET
External
NET
External
NET
External
1: EXT
Remarks
1:
2:
EXT
EXT
NET
EXT
EXT
External
Pr.59 = "0" (multi-
speed), Pr.59 ≠ "0"
(remote), Pr.270 ="1,
External
3, 11, or 13" (stop-
on-contact)
External
Pr.270 ="1, 3, 11, or
13" (stop-on-contact)
Combined
Pr.59 ="0" (multi-
External
speed)
External
Pr.79 ≠ "7"
Pr.79 = "7"
When X12 signal is
not assigned.