Mitsubishi Electric FR-A820-00046 (0.4K) Instruction Manual page 343

Fr-a800 series
Hide thumbs Also See for FR-A820-00046 (0.4K):
Table of Contents

Advertisement

*2
The setting is available only for standard models and IP55 compatible models.
 Life alarm display and signal output (Y90 signal, Pr.255)
• In the life diagnosis of the main circuit capacitor, the alarm signal (Y90) is not output unless measurement by turning OFF the
power supply is performed.
• Whether or not the parts of the control circuit capacitor, main circuit capacitor, cooling fan, inrush current limit circuit or
internal air circulation fans have reached the life alarm output level can be checked with Pr.255 Life alarm status display
and the Life alarm (Y90) signal. (Internal air circulation fans are equipped with IP55 compatible models.)
bit
15
0 0 0 0 0 0 0 0 0 0 0 0 1 0 0
Pr.255
Decimal
Binary
15
1111
14
1110
13
1101
12
1100
11
1011
10
1010
9
1001
8
1000
7
0111
6
0110
5
0101
4
0100
3
0011
2
0010
1
0001
0
0000
○: With warnings, ×: Without warnings
• The Life alarm (Y90) signal turns ON when any of the control circuit capacitor, main circuit capacitor, cooling fan, inrush
current limit circuit or internal air circulation fans reaches the life alarm output level.
• For the terminal used for the Y90 signal, set "90" (positive logic) or "190" (negative logic) in any of Pr.190 to Pr.196 (output
terminal function selection).
NOTE
• When using an option (FR-A8AY, FR-A8AR, FR-A8NC, FR-A8NCE), the life can be output separately to the Control circuit
capacitor life (Y86) signal, Main circuit capacitor life (Y87) signal, Cooling fan life (Y88) signal, and Inrush current limit circuit
life (Y89) signal.
• Changing the terminal assignment using Pr.190 to Pr.196 (Output terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
 Life display of the inrush current limit circuit (Pr.256) (Standard models
and IP55 compatible models)
• The life of the inrush current limit circuit (relay, contactor and inrush resistor) is displayed in Pr.256.
342
5. PARAMETERS
5.7 (E) Environment setting parameters
7
0
1
bit0 Control circuit capacitor life
bit1 Main circuit capacitor life
(Standard models and IP55 compatible models only)
bit2 Cooling fan life
bit3 Inrush current limit circuit life
(Standard models and IP55 compatible models only)
bit4 Life of internal air circulation fans (IP55 compatible models only)
bit4
bit3
bit2
bit1
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
• Pr.255 read
Pr.255
bit0
Decimal
Binary
31
11111
×
30
11110
29
11101
×
28
11100
27
11011
×
26
11010
25
11001
×
24
11000
23
10111
×
22
10110
21
10101
×
20
10100
19
10011
×
18
10010
17
10001
×
16
10000
• Pr.255 setting read
Bit image is displayed
in decimal
bit4
bit3
bit2
bit1
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
bit0
×
×
×
×
×
×
×
×