Mitsubishi Electric FR-A820-00046 (0.4K) Instruction Manual page 732

Fr-a800 series
Hide thumbs Also See for FR-A820-00046 (0.4K):
Table of Contents

Advertisement

• The reply code (RWr10) to the instruction code execution is set in D2. (Refer to
SB49
SW0B0.0
0
M0
X20
3
M300
7
M301
X1025
9
M302
X1025
16
24
NOTE
• For the parameter assigned the number of 100 or higher, change the link parameter extended setting (set it to the one other
than H00). Refer to
 Programming example for the parameter writing
The following program changes the setting value in Pr.7 Acceleration time of the station 1 inverter to 3.0 s.
• Acceleration time writing instruction code: H87 (hexadecimal)
• Acceleration time setting data: K30 (decimal)
For the details of instruction codes of each parameter, refer to the list of parameters (function codes) and instruction codes
under different control modes (on
The reply code (RWr10) to the instruction code execution is set in D2. (Refer to
SB49
SW0B0.0
0
M0
X20
3
M300
7
M301
X1025
9
M302
X1025
18
24
NOTE
• For the parameter assigned the number of 100 or higher, change the link parameter extended setting (set it to the one other
than H00). Refer to
• For other functions, refer to the instruction codes (refer to
 Programming example for setting the running frequency
The following program changes the running frequency of the station 1 inverter to 50.00 Hz.
• Set frequency: K5000 (decimal)
M0
Check the data link status of the station 1.
PLS M300
SET M301
MOV H7
W110
Write the Pr. 7 read code (H07) to RWw10.
SET Y1025
Turn ON the instruction code execution request (RY25).
RST M301
SET M302
Read the acceleration time (RWr11) and the reply code
MOV W11 D1
(RWr10) to output to D1 and D2 when the instruction code
execution completion (RX25) turns ON.
MOV W10 D2
RST Y1025
Turn OFF the instruction code execution request (RY25).
RST M302
END
page 824
for the settings.
page
824).
M0
Check the data link status of the station 1.
PLS M300
SET M301
MOV H87 W110
Write the Pr. 7 write code (H87) to RWw10 and
the acceleration time setting data (K30) to RWw11.
MOV K30 W111
SET Y1025
Turn ON the instruction code execution request (RY25).
RST M301
SET M302
Read the reply code (RWr10) to output to D2 when the
MOV W10 D2
instruction code execution completion (RX25) turns ON.
Turn OFF the instruction code execution request (RY25).
RST Y1025
RST M302
END
page 824
for the settings.
page 724
page 724
for the reply code (RWr10).)
page
724).
5.21 CC-Link IE Field Network (FR-A800-GF)
for the reply code (RWr10).)
5. PARAMETERS
1
2
3
4
5
6
7
8
9
10