Mitsubishi Electric FR-A820-00046 (0.4K) Instruction Manual page 619

Fr-a800 series
Hide thumbs Also See for FR-A820-00046 (0.4K):
Table of Contents

Advertisement

Pr.
1038
Digital source selection
A930
(1ch)
1039
Digital source selection
A931
(2ch)
1040
Digital source selection
A932
(3ch)
1041
Digital source selection
A933
(4ch)
1042
Digital source selection
A934
(5ch)
1043
Digital source selection
A935
(6ch)
1044
Digital source selection
A936
(7ch)
1045
Digital source selection
A937
(8ch)
1046
Digital trigger channel
A938
1047
Digital trigger operation
A939
selection
 Operation outline
• This function samples the status (analog monitor and digital monitor) of the inverter, traces the sampling data when a
trigger (trace start condition) is generated, and saves the resulting trace data.
• When the trace function is set enabled, samplings are collected and the inverter goes into the pre-trigger status.
• In the pre-trigger status, samples are collected, and the trigger standby status is entered when sufficient samples for the
number of pre-trigger samples have been collected.
• When the trigger is generated in the trigger standby status, the trace is started and the trace data is saved.
Sampling start
Sampling data
0%
Sampling start
Sampling data
Sampling start
Sampling data
 Selection of trace mode (Pr.1021)
• Select how to save the trace data which results from sampling the inverter status.
618
5. PARAMETERS
5.14 (A) Application parameters
Name
Initial value
1
2
3
4
5
6
7
8
1
0
Data in the period
is discarded.
0%
Data in the period
is discarded.
Trace start
0%
Setting
range
1 to 255
Select the digital data (I/O signal) for sampling on each channel.
1 to 8
Select the digital channel to be the trigger.
0
Trace starts when the signal turns ON
1
Trace starts when the signal turns OFF
If the data is short for the pre-trigger sampling,
the inverter goes into the pre-trigger state.
Pre-trigger sampling number
90%
Once the enough data is collected for trigger sampling,
the inverter goes into the trigger-ready state.
Pre-trigger sampling number
At trigger generation, samples equivalent to the 100%
pre-trigger sampling number are collected and saved.
Description
90%
100%
A trigger occurs
Trace completed
90%
100%

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-a820-00167 (2.2k)Fr-a820-00046-gf (0.4k)Fr-a820-00250 (3.7k)Fr-a820-00105-gf (1.5k)Fr-a820-00077 (0.75k)Fr-a820-00250-gf (3.7k) ... Show all

Table of Contents