Limiting The Output Frequency (Maximum/Minimum Frequency) - Mitsubishi Electric FR-A820-00046 (0.4K) Instruction Manual

Fr-a800 series
Hide thumbs Also See for FR-A820-00046 (0.4K):
Table of Contents

Advertisement

CAUTION
• When the retry function is set enabled, stay away from the motor and machine in the case of an output shutoff. The motor
and machine will start suddenly (after the reset time has elapsed) after the shutoff. When the retry function is selected,
apply the supplied CAUTION stickers to easily visible places.
Parameters referred to
Pr.57 Restart coasting
timepage
5.10.9 Limiting the output frequency (maximum/minimum
frequency)
Motor speed can be limited. Clamp the upper and lower limits of the output frequency.
Pr.
Name
1
Maximum frequency
H400
2
Minimum frequency
H401
18
High speed maximum
H402
frequency
*1
For the FR-A820-03160(55K) or lower, and FR-A840-01800(55K) or lower.
*2
For the FR-A820-03800(75K) or higher, and FR-A840-02160(75K) or higher.
 Setting the maximum frequency (Pr.1, Pr.18)
• Set Pr.1 Maximum frequency to the upper limit of the output frequency. If the value of the frequency command given is
higher than the setting, the output frequency is clamped at the maximum frequency.
• To operate at a frequency higher than the 120 Hz, adjust the upper output frequency limit with Pr.18 High speed
maximum frequency. (When setting a frequency in Pr.18, the Pr.1 setting automatically changes to the frequency set in
Pr.18. Also, when setting a frequency in Pr.1, the Pr.18 setting automatically changes to the frequency set in Pr.1.)
Output frequency
(Hz)
Pr.1
Pr.18
Pr.2
0
(4mA)
Clamped at the
minimum frequency
 Setting the minimum frequency (Pr.2)
• Set Pr.2 Minimum frequency to the lower limit of the output frequency.
• If the set frequency is Pr.2 or less, the output frequency is clamped at Pr.2 (does not fall below Pr.2).
NOTE
• To operate with a frequency higher than 60 Hz using frequency-setting analog signals, change the Pr.125 (Pr.126) (frequency
setting gain) setting. Simply changing the Pr.1 and Pr.18 settings does not enable the operation at a frequency higher than
60 Hz.
• During Real sensorless vector control, Vector control, and PM sensorless vector control, the upper and lower limits are for the
commanded frequency. The final output frequency that is decided by each control may exceed the lower or upper limits.
• When Pr.15 Jog frequency is equal to or less than Pr.2, the Pr.15 setting takes precedence.
• If a jump frequency that exceeds Pr.1 (Pr.18) is set for the 3-point frequency jump, the maximum frequency setting is the set
frequency. If the jump frequency is less than the setting of Pr.2, the jump frequency is the set frequency. (The set frequency
can be equal to or lower than the frequency lower limit.) When stall prevention is activated to decrease the output frequency,
the output frequency may drop to Pr.2 or below.
597,
page 604
Initial value
*1
120 Hz
0 to 120 Hz
*2
60 Hz
0 Hz
0 to 120 Hz
*1
120 Hz
0 to 590 Hz
*2
60 Hz
Clamped at the
maximum frequency
Frequency setting
5, 10V
(20mA)
Setting range
Set the upper limit of the output frequency.
Set the lower limit of the output frequency.
Set when operating at 120 Hz or higher.
Description
5. PARAMETERS
5.10 (H) Protective function parameter
1
2
3
4
5
6
7
8
9
10
407

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-a820-00167 (2.2k)Fr-a820-00046-gf (0.4k)Fr-a820-00250 (3.7k)Fr-a820-00105-gf (1.5k)Fr-a820-00077 (0.75k)Fr-a820-00250-gf (3.7k) ... Show all

Table of Contents