Mitsubishi Electric FR-A820-00046 (0.4K) Instruction Manual page 670

Fr-a800 series
Hide thumbs Also See for FR-A820-00046 (0.4K):
Table of Contents

Advertisement

Restore
GOT2000
 Connected devices
• To enable backup/restore, connect either the general-purpose inverter with the FR-A8NCE or the FR-A800-GF inverter to
a programmable controller (master station) via the CC-Link IE Field Network.
NOTE
• The backup/restore function is enabled only when the inverter is connected to a master station programmable controller.
• For the details of the connected devices, refer to the GOT2000 Series User's Manual (Monitor).
 Data to be backed up and restored
• The following data can be backed up and restored. The data other than those listed below cannot be backed up or restored.
Inverter parameters
Parameters used for activating the PLC function
Programs (including SFCs) used in the PLC function
Global device comment information used in the PLC function
Function block source information
 Backup/restore operation
• The GOT backs up all applicable data in all the inverters that can be identified with the network numbers and station
numbers in the controller list file.
• The GOT restores all relevant data of the inverters selected based on the network numbers and station numbers using the
backup data.
• The backup/restore cannot be performed in the following cases.
Operation
Backup
During an inverter reset
A password is registered or password protection is enabled (Pr.297 ≠ "9999").
During parameter copy using an operation panel or USB memory device (during writing to the inverter)
During restore
While password protection is enabled for files used in the PLC function (read protection)
While PLC function project data is written to, read from, or verified against a USB memory device
Restore
During an inverter reset
During running
During auto tuning
A password is registered or password protection is enabled (Pr.297 ≠ "9999").
While parameter write is disabled (Pr.77 = "1")
During parameter copy using an operation panel or USB memory device (during writing to / reading from /
verification against the inverter)
During backup operation
During the RUN status of the PLC function
While password protection is enabled for files used in the PLC function (write protection)
While PLC function project data is written to, read from, or verified against a USB memory device
• On the operation panel, "RD" is displayed during backup, and "WR" is displayed during restore.
Ethernet
CC-Link IE Field Network
MELSEC iQ-R
Item
Backup
FR-A800 (with the FR-A8NCE installed)
FR-A800-GF
Inverter status
5.15 (N) Communication operation parameters
1
2
3
4
5
6
7
8
9
10