5.21

CC-Link IE Field Network (FR-A800-GF)

5.21.1 Cyclic transmission

Data communication is available periodically among stations on the same network. Link devices (RX, RY, RWr, and RWw) are
used.
 Data flow and link device assignment (master and slave stations (except
for local stations))
One-to-one communication is possible between the master and slave stations.
The status information of the link devices (RY and RWw) of the master station is output to the external device of the slave
station, and the input status information from the external device of the slave station is stored in the link devices (RX and RWr)
of the master station.
Status
Output from the master
station
Input from the slave
station
716
5. PARAMETERS
5.21 CC-Link IE Field Network (FR-A800-GF)
Station No.0
CPU
Master
module
station
Device
RX, RWr
(7)
Station
No.1
Sequence
Sequence
Sequence
scan
scan
scan
Station
Link refresh
No.2
Device
RY, RWw
Station
(2)
No.1
Sequence
Sequence
Sequence
scan
scan
scan
Station
Link refresh
No.2
M0
(1)
1
Y
No.
(1)
The device of the CPU module turns ON.
The device status data of the CPU module are stored in the link devices (RY and RWw) of the master
(2)
station by link refresh.
The status data of the link devices (RY and RWw) of the master station are stored in the link devices (RY
(3)
and RWw) of each slave station by link scan.
The inverter starts according to the link device (RY and RWw) conditions (input signals such as STF and
(4)
STR) of the slave station.
Inverter conditions (output signals such as RUN and SU, monitoring) are stored in the link devices (RX and
(5)
RWr) of the slave station.
The status data of the link devices (RX and RWr) of the slave station are stored in the link devices (RX and
(6)
RWr) of the master station by link scan.
The status data of the link devices (RX and RWr) of the master station are stored in the devices of the CPU
(7)
module by link refresh.
Station No.1
Slave station
(5)
RX, RWr
(6)
Station No.1
(6)
Link
scan
(4)
RY, RWw
(3)
Station No.1
(3)
Area for sending to
other stations
Description
Station No.2
Slave station
(5)
RX, RWr
Station No.2
(4)
RY, RWw
Station No.2