Mitsubishi Electric FR-A820-00046 (0.4K) Instruction Manual page 572

Fr-a800 series
Hide thumbs Also See for FR-A820-00046 (0.4K):
Table of Contents

Advertisement

Pr.
Name
610
PID measured value
A625
input selection
1015
Integral stop selection at
A607
limited frequency
753
Second PID action
A650
selection
Second PID control
754
automatic switchover
A652
frequency
755
Second PID action set
A651
point
756
Second PID proportional
A653
band
757
Second PID integral time 1 s
A654
758
Second PID differential
A655
time
1140
Second PID set point/
A664
deviation input selection
1141
Second PID measured
A665
value input selection
1143
Second PID upper limit
A641
1144
Second PID lower limit
A642
1145
Second PID deviation
A643
limit
1146
Second PID signal
A644
operation selection
Second output
1147
interruption detection
A661
time
Second output
1148
interruption detection
A662
level
1149
Second output
A663
interruption cancel level
Initial value
Setting range
1
2
3
3
4
5
0
1
2
0
10
11
12
0, 10, 11, 20, 21,
50, 51, 60, 61, 70,
71, 80, 81, 90, 91,
0
100, 101, 1000,
1001, 1010,
1011, 2000,
2001, 2010, 2011
9999
0 to 590 Hz, 9999 Refer to Pr.127.
9999
0 to 100%, 9999
0.1 to 1000%,
100
9999
0.1 to 3600 s,
9999
9999
0.01 to 10 s, 9999 Refer to Pr.134.
2
1 to 5
3
1 to 5
9999
0 to 100%, 9999
9999
0 to 100%, 9999
9999
0 to 100%, 9999
0
0 to 3, 10 to 13
1 s
0 to 3600 s, 9999 Refer to Pr.575.
0 Hz
0 to 590 Hz
1000%
900 to 1100%
Description
Input of measured value from terminal 1
Input of measured value from terminal 2
Input of measured value from terminal 4
Input of set point, deviation value via CC-Link/CC-Link IE Field
Network communication
Input measured value by PLC function
Integral stopped at the limit, manipulation range of ±100%, integral
cleared during output interruption
Integral continued at the limit, manipulation range of ±100%,
integral cleared during output interruption
Integral stopped at the limit, manipulation range of 0 to 100%,
integral cleared during output interruption
Integral stopped at the limit, manipulation range of ±100%, integral
stopped during output interruption
Integral continued at the limit, manipulation range of ±100%,
integral stopped during output interruption
Integral stopped at the limit, manipulation range of 0 to 100%,
integral stopped during output interruption
Refer to Pr.128.
Refer to Pr.133.
Refer to Pr.129.
Refer to Pr.130.
Set the second PID control.
Refer to Pr.609.
For how to enable the second PID
control, refer to
Refer to Pr.610.
Refer to Pr.131.
Refer to Pr.132.
Refer to Pr.553.
(The Y205 signal is
output.)
Refer to Pr.554.
Refer to Pr.576.
Refer to Pr.577.
page
582.
5. PARAMETERS
5.14 (A) Application parameters
1
2
3
4
5
6
7
8
9
10
571

Hide quick links:

Advertisement

Table of Contents
loading