Pr.
Name
22
Stall prevention
H500
operation level
156
Stall prevention
H501
operation selection
Second stall
48
prevention operation
H600
level
Second stall
49
prevention operation
H601
frequency
114
Third stall prevention
H602
operation level
115
Third stall prevention
H603
operation frequency
Stall prevention
23
operation level
H610
compensation factor at
double speed
Stall prevention
66
operation reduction
H611
starting frequency
148
Stall prevention level at
H620
0 V input
149
Stall prevention level at
H621
10 V input
Voltage reduction
154
selection during stall
H631
prevention operation
157
OL signal output timer
M430
858
Terminal 4 function
T040
assignment
868
Terminal 1 function
T010
assignment
*1
The upper limit of stall prevention operation is limited internally to the following.
120% (SLD rating), 150% (LD rating), 220% (ND rating), or 280% (HD rating)
410
5. PARAMETERS
5.10 (H) Protective function parameter
Initial value
Setting range
FM
CA
0
150%
*1
0.1 to 400%
0
0 to 31, 100, 101
0
150%
*1
0.1 to 400%
0
0 Hz
0.01 to 590 Hz
9999
0
150%
*1
0.1 to 400%
0
0 Hz
0.01 to 590 Hz
0 to 200%
9999
9999
60 Hz
50 Hz
0 to 590 Hz
*1
150%
0 to 400%
*1
200%
0 to 400%
0
1
1
10
11
0 to 25 s
0 s
9999
0
0, 1, 4, 9999
0
0 to 6, 9999
Description
Stall prevention operation disabled.
Set the current limit at which the stall prevention operation
starts.
Enable/disable the stall prevention operation and the fast-
response current limit operation.
Second stall prevention operation disabled.
The stall prevention operation level can be changed using the
RT signal.
Second stall prevention operation disabled.
Set the frequency at which the Pr.48 stall prevention
operation starts.
Pr.48 is enabled when the RT signal is ON.
Third stall prevention operation disabled.
The stall prevention operation level can be changed using the
X9 signal.
Third stall prevention operation disabled.
Set the frequency at which the stall prevention operation
starts when the X9 signal turns ON.
The stall operation level when running at high speeds above
the rated frequency can be reduced.
Stall prevention operation disabled at double speed.
Set the frequency at which the stall operation level reduction
starts.
The stall prevention operation level can be changed by the
analog signal input to the terminal 1 (terminal 4).
Output voltage reduction
Enable/disable the output
enabled
voltage reduction during stall
Output voltage reduction
prevention operation.
disabled.
Output voltage reduction
Use this setting when the
enabled
overvoltage protective function
(E.OV[]) is activated during stall
prevention operation in an
Output voltage reduction
application with large load
disabled.
inertia.
Set the OL signal output start time when stall prevention is
activated.
No OL signal output.
When set "4", the stall prevention level can be changed with
the signal to the terminal 4.
When set "4", the stall prevention level can be changed with
the signal to the terminal 1.