Mitsubishi Electric FR-A820-00046 (0.4K) Instruction Manual page 662

Fr-a800 series
Hide thumbs Also See for FR-A820-00046 (0.4K):
Table of Contents

Advertisement

• Inverter status / control input command
Bit
Control input command
0
Stop command
1
Forward rotation command
2
Reverse rotation command
3
RH (High-speed operation command)
4
RM (Middle-speed operation command)
5
RL (Low-speed operation command)
6
JOG (Jog operation selection)
7
RT (Second function selection)
8
AU (Terminal 4 input selection)
CS (Selection of automatic restart after
9
instantaneous power failure / flying start)
*4*5
10
MRS (Output stop)
11
STP (STOP) (Start self-holding selection)
*4
12
RES (Inverter reset)
13
0
14
0
15
0
*4
The signal within parentheses ( ) is the initial status. The description changes depending on the setting of Pr.180 to Pr.189 (Input terminal
function selection)
The signals assigned to the input terminals may be valid or invalid in the NET operation mode. (Refer to
*5
The Inverter run enable signal is in the initial status for the separated converter type.
*6
The signal within parentheses ( ) is the initial status. The description changes depending on the setting of Pr.190 to Pr.196 (Output terminal
function selection)
*7
No function is assigned in the initial status for the separated converter type.
• Operation mode / inverter setting
Mode
EXT
PU
EXT
JOG
PU
JOG
NET
PU + EXT
*8
Writing is available depending on the Pr.79 and Pr.340 settings. For the details, refer to
Restrictions in each operation mode conform with the computer link specification.
• Real time monitor
Refer to
page 424
for the register numbers and monitor items of the real time monitor.
• Parameters
Pr.
Register
For details on parameter names,
41000 to
0 to 999
refer to the parameter list
41999
162).
Terminal 2 frequency setting bias
C2 (902)
41902
(frequency)
Terminal 2 frequency setting bias
42092
(analog value)
C3 (902)
Terminal 2 frequency setting bias
43902
(terminal analog value)
Terminal 2 frequency setting gain
125 (903)
41903
(frequency)
Definition
RUN (Inverter running)
Forward running
Reverse running
*4
SU (Up to frequency)
*4
OL (Overload warning)
IPF (Instantaneous power failure/
*4
undervoltage)
*4
FU (Output frequency detection)
*4
ABC1 (Fault)
*4
ABC2 (-)
Safety monitor output
*4
0
*4
0
0
0
0
Fault occurrence
(page
496).
(page
450).
Read value
H0000
H0001
H0002
H0003
H0004
H0005
Name
(page
Read/write
Read/write
Read/write
Read
Read/write
Inverter status
*6
*6
*6
*6*7
*6
*6
*6
Write value
*8
H0010
*8
H0011
H0014
page
378.
Read/write
The parameter number + +41000 is the register number.
Analog value (%) set to C3 (902)
Analog value (%) of the voltage (current) applied to
terminal 2
5.15 (N) Communication operation parameters
page
384.)
Remarks
5. PARAMETERS
1
2
3
4
5
6
7
8
9
10