Allow clearance.
*1
For the FR-A820-00250(3.7K) or lower and FR-A840-00126(3.7K) or lower, allow 1 cm or more clearance.
*2
When using the FR-A820-01250(22K) or lower and FR-A840-00620(22K) or lower at the surrounding air temperature of 40°C or less (30°C or
less for the SLD rated inverter), side-by-side installation (0 cm clearance) is available.
*3
For replacing the cooling fan of the FR-A840-04320(160K) or higher, 30 cm of space is necessary in front of the inverter. Refer to
fan replacement.
 Installation orientation of the inverter
Install the inverter on a wall as specified. Do not mount it horizontally or in any other way.
 Above the inverter
Heat is blown up from inside the inverter by the small fan built in the unit. Any equipment placed above the inverter should be
heat resistant.
 Arrangement of multiple inverters
When multiple inverters are placed in the same enclosure, generally arrange them horizontally as shown in the figure (a). When
it is inevitable to arrange them vertically to minimize space, take such measures as to provide guides since heat from the bottom
inverters can increase the temperatures in the top inverters, causing inverter failures.
When mounting multiple inverters, fully take caution not to make the surrounding air temperature of the inverter higher than the
permissible value by providing ventilation and increasing the enclosure size.
Inverter
Inverter
Enclosure
(a) Horizontal arrangement
Arrangement of multiple inverters
FR-A820-03160(55K) or lower,
FR-A840-01800(55K) or lower
5 cm
*1,*2
or more
Vertical
Inverter
Inverter
Guide
Guide
Guide
Inverter
Inverter
Enclosure
(b) Vertical arrangement
Clearances (front)
FR-A820-03800(75K) or higher,
FR-A840-02160(75K) or higher
20 cm
10 cm
or more
or more
5 cm
10 cm
*1,*2
or more
or more
10 cm
20 cm
or more
or more
2.3 Installation of the inverter and enclosure design
Clearances (side)
5 cm
10 cm
or more
*1,*3
or more
Inverter