2 Installation and commissioning
2.4.2 Installation, IRC5 Panel Mounted Controller
Continued
Installing the modules in a cabinet
The IRC5 Panel Mounted Controller modules should be mounted on a rack system
in a cabinet. The recommended minimum depth of the cabinet is 400 mm for PMC
small and 500 mm for PMC large. The cabinet must fulfill the requirements specified
in
The following procedure details how to install the IRC5 Panel Mounted modules.
1
2
3
Mounting the FlexPendant holder
The FlexPendant holder is available in different versions, that fit different
FlexPendant versions. The holder is compatible with the FlexPendant that it is
delivered with.
Continues on next page
56
Protection class on page
Action
Fit the module on pre-mounted M5 screws (4 pcs).
Secure the module with new M5 screws (4 pcs).
Fasten the module (M5 screw, 8 pcs)
© Copyright 2007-2024 ABB. All rights reserved.
46.
Product manual - IRC5 Panel Mounted Controller
Note/Illustration
xx0600003452
A: M5 screws (4 pcs)
xx0600003453
B: M5 screws (4 pcs)
Tightening torque 4,5 Nm.
3HAC047137-001 Revision: AB