AC current in CP/CS
For specific applications where the correct cable dimensioning can depend on the
relationship between the period of the duty cycle and the thermal time constant of
the cable (for example, starting against high-inertia load, intermittent duty), the
cable manufacturer can provide information.
Country specific norms have to be included.
The wire is not dimensioned to take care of starting motors or transformers.
The following table shows how much AC current can be supplied with a specific
temperature, and the wire size.
Wire size (mm
Single wire 0.2//24
Multi wire 2 pair 0.2//24
Multi wire 4 pair 0.2//24
Multi wire 6 pair 0.2//24
Multi wire 9 pair 0.2//24
Single wire 0.5//20
Multi wire 2 pair 0.5//20
Multi wire 4 pair 0.5//20
Multi wire 6 pair 0.5//20
Multi wire 9 pair 0.5//20
Single wire 0.75//18
Multi wire 2 pair 0.75//18
Multi wire 4 pair 0.75//18
Multi wire 6 pair 0.75//18
Multi wire 9 pair 0.75//18
Single wire 1.0//17
Multi wire 2 pair 1.0//17
Multi wire 4 pair 1.0//17
Multi wire 6 pair 1.0//17
Multi wire 9 pair 1.0//17
0.75//18 three phase
1.0//17 three phase
Product manual - IRC5 Panel Mounted Controller
3HAC047137-001 Revision: AB
Note
Any local standards and regulations concerning insulation and area must always
be complied with.
2
//AWG)
© Copyright 2007-2024 ABB. All rights reserved.
2 Installation and commissioning
2.5.1 Connecting cables to the controller
AC current
40°C//104F
45°C//113F
4.5
4.1
3.6
3.3
2.9
2.7
2.6
2.3
2.3
2.0
7.9
7.2
6.3
5.8
5.1
4.7
4.5
4.1
4.0
3.6
9.5
8.6
7.6
6.9
6.2
5.6
5.4
4.9
4.8
4.3
11.0
10.0
8.8
8.0
7.2
6.5
6.3
5.7
5.5
5.0
8.6
7.8
10.3
9.4
Continued
50°C//122F
52°C//125.6F
3.7
3.2
3.0
2.6
2.4
2.1
2.1
1.8
1.8
1.6
6.5
5.6
5.2
4.5
4.2
3.6
3.7
3.2
3.2
2.8
7.8
6.7
6.2
5.4
5.1
4.4
4.4
3.8
3.9
3.4
9.0
7.8
7.2
6.2
5.9
5.1
5.1
4.5
4.5
3.9
7.1
5.6
8.4
6.7
Continues on next page
59