ABB IRC5 Product Manual page 63

Panel mounted controller
Hide thumbs Also See for IRC5:
Table of Contents

Advertisement

Example 1:
Example 2:
Interference elimination
Internal relay coils and other units that can generate interference inside the control
cabinet are neutralized. External relay coils, solenoids and other units must be
clamped in a similar way. The illustration below shows how this can be done.
Note that the turn-off time for DC relays increases after neutralization, especially
if a diode is connected across the coil. Varistors give shorter turn-off times.
Neutralizing the coils lengthens the life of the switches that control them.
xx1200000961
Product manual - IRC5 Panel Mounted Controller
3HAC047137-001 Revision: AB
Where a good earth connection is available on all units, the best shielding
is obtained by grounding all screens at both ends on all units.
If the cable is terminated where a good earth connection is not available a
noise suppression capacitor can be used. The screens of the 2 cables must
be connected as shown in the figure, but not connected to the chassis of the
unit.
+24 V DC
+24 V AC/DC
1 The diode should be dimensioned for the same current as the relay coil, and
a voltage of twice the supply voltage.
2 The varistor should be dimensioned for the same energy as the relay coil,
and a voltage of twice the supply voltage.
3 When AC voltage is used, the components needs to be dimensioned for >500
V max voltage and 125 V nominal voltage.
The resistor should be 100 Ω, and the capacitor should be 1W 0.1 - 1 µF
(typically 0.47 µF).
© Copyright 2007-2024 ABB. All rights reserved.
2 Installation and commissioning
2.5.1 Connecting cables to the controller
0 V
1)
2)
0 V
3)
Continued
63

Advertisement

Table of Contents
loading

Table of Contents