Group
46 FAULT FUNCTIONS
Definition of drive behaviour upon a fault situation.
An alarm or a fault message indicates abnormal drive status. For the possible
causes and remedies, see chapter
46
46 FAULT FUNCTIONS
Firmware block:
FAULT FUNCTIONS
(46)
This block
• configures supervision of external
faults by defining the source (for
example, a digital input) for external
fault indication signal
• selects the reaction of the drive
(alarm; fault; continuation at safe
speed in some cases) upon
situations like local control
communication break, motor/supply
phase loss, earth fault, or Safe
Torque Off function activation
• shows the codes of the latest faults,
the time at which the active fault
occurred, and the alarm words.
Block outputs located in other
parameter groups
46.01 EXTERNAL FAULT
Selects an interface for an external fault signal. 0 = External fault trip. 1 = No external fault.
Bit pointer: Group, index and bit
46.02 SPEED REF SAFE
Defines the fault speed. Used as a speed reference when an alarm occurs when parameter
SUPERVISION
SAFE.
-30000...30000 rpm
46.03 LOCAL CTRL LOSS
Selects how the drive reacts to a control panel or PC tool communication break.
(0) NO
[ TRUE ]
[ 0 rpm ]
[ Fault ]
[ Fault ]
[ Fault ]
[ Fault ]
[ Fault ]
[ Fault ]
8.01 ACTIVE FAULT
8.02 LAST FAULT
8.03 FAULT TIME HI
8.04 FAULT TIME LO
8.05 ALARM WORD 1
8.06 ALARM WORD 2
8.07 ALARM WORD 3
8.08 ALARM WORD 4
FW block:
FW block:
/
46.03 LOCAL CTRL LOSS
Fault speed.
FW block:
No action.
Fault
tracing.
FAULT FUNCTIONS
TLF10 2 msec
8.01 ACTIVE FAULT
8.02 LAST FAULT
8.03 FAULT TIME HI
8.04 FAULT TIME LO
8.05 ALARM WORD 1
8.06 ALARM WORD 2
8.07 ALARM WORD 3
8.08 ALARM WORD 4
< 46.01 EXTERNAL FAULT
46.02 SPEED REF SAFE
46.03 LOCAL CTRL LOSS
46.04 MOT PHASE LOSS
46.05 EARTH FAULT
46.06 SUPPL PHS LOSS
46.07 STO DIAGNOSTIC
46.08 CROSS CONNECTION
(page 99)
(page 99)
(page 99)
(page 99)
(page 99)
(page 100)
(page 100)
(page 100)
FAULT FUNCTIONS
(see above)
FAULT FUNCTIONS
(see above)
/
50.02 COMM LOSS FUNC
FAULT FUNCTIONS
(see above)
Parameters and firmware blocks
33
(10)
13.12 AI
setting is
(2) SPD REF
173

Advertisement

Table of Contents