Gain Adjustment Of Current Controllers For The D Axis And The Q Axis - Mitsubishi Electric FR-A800 Series Instruction Manual

Hide thumbs Also See for FR-A800 Series:
Table of Contents

Advertisement

Pr.
854
Excitation ratio
G217
Excitation ratio
[%]
100
(Initial value)
Pr.854
setting
0
NOTE
• When excitation ratio is reduced, output torque startup is less responsive.
• The setting of Pr.854 is invalid if Pr.858 Terminal 4 function assignment or Pr.868 Terminal 1 function assignment is set
to "1" (flux command according to terminal).
5.6.3
PM
PM
PM
The gain of the current controller can be adjusted.
Pr.
824
Torque control P gain 1 (current
G213
loop proportional gain)
825
Torque control integral time 1
G214
(current loop integral time)
• Use Pr.824 Torque control P gain 1 (current loop proportional gain) to adjust the proportional gain of current
controllers for the d axis and the q axis. The 100% gain is equivalent to 1000 rad/s. Setting this parameter higher improves
the trackability for current command changes. It also reduces the current fluctuation caused by external disturbances.
• Use Pr.825 Torque control integral time 1 (current loop integral time) to set the integral time of current controllers for
the d axis and the q axis. If the setting value is small, it produces current fluctuation against external disturbances,
decreasing time until it returns to original current value.
NOTE
• Pr.834 Torque control P gain 2 (current loop proportional gain) and Pr.835 Torque control integral time 2 (current loop
integral time) are valid when the RT signal turns ON.
In this case, replace them for Pr.824 and Pr.825 in the description above.
Downloaded from
ManualsNet.com
Name
Initial value
100%
100
Gain adjustment of current controllers for the d
axis and the q axis
Name
100%
5 ms
5.6 Adjustment during Real sensorless vector control, Vector control, PM sensorless vector control
search engine
Setting
range
0 to 100%
Set an excitation ratio when there is no load.
Load[%]
Initial
Setting
value
range
0% to 500%
The proportional gain of the current controller is set.
0 to 500 ms
The integral time of the current controller is set.
Description
Description
5. PARAMETERS
1
2
3
4
5
6
7
8
9
10
333