Mitsubishi Electric FR-A800 Series Instruction Manual page 400

Hide thumbs Also See for FR-A800 Series:
Table of Contents

Advertisement

 Selecting the operation mode for power-ON (Pr.340)
• Depending on the Pr.79 and Pr.340 settings, the operation mode at power-ON (reset) changes as described below.
Pr.340
setting
0 (initial
value)
*1
1, 2
*1
10, 12
*1
Use Pr.340 = "2 or 12" setting to perform communication with the RS-485 terminals. Even if an instantaneous power failure occurs while Pr.57
Restart coasting time ≠ "9999", the inverter continues running at the condition before the instantaneous failure. When Pr.340 = "1 or 10", if a
power failure occurs while the start signal is being input through communication, the start signal is OFF at power restoration.
*2
The operation mode cannot be directly changed between the PU operation mode and Network operation mode.
*3
Switching between the PU and NET operation modes is available with the
Parameters referred to
Pr.57 Restart coasting
Pr.79 Operation mode
Downloaded from
ManualsNet.com
Pr.79
Operation mode at power-ON, at
setting
power restoration, or after a reset
0 (initial
External operation mode
value)
1
PU operation mode
2
External operation mode
3, 4
External/PU combined operation mode
6
External operation mode
X12 (MRS) signal ON: External
operation mode
7
X12 (MRS) signal OFF: External
operation mode
0
NET operation mode
1
PU operation mode
2
NET operation mode
3, 4
External/PU combined operation mode
6
NET operation mode
X12 (MRS) signal ON: NET operation
mode
7
X12 (MRS) signal OFF: External
operation mode
0
NET operation mode
1
PU operation mode
2
NET operation mode
3, 4
External/PU combined operation mode
6
NET operation mode
7
External operation mode
timepage
628,
page 635
selectionpage 389
search engine
Operation mode switching
Switching among the External, PU, and NET operation modes is
*2
enabled
Fixed at PU operation mode.
Switching between the External and NET operation modes is enabled.
Switching to PU operation mode is disabled.
Operation mode switching is disabled.
Switching among the External, PU, and NET operation mode is
enabled while running.
Switching among the External, PU, and NET operation modes is
*2
enabled
Fixed at External operation mode (forcibly switched to External
operation mode).
Same as Pr.340 = "0".
Switching between the PU and NET operation mode is enabled.
Same as Pr.340 = "0".
Fixed at NET operation mode.
Same as Pr.340 = "0".
Switching between the PU and NET operation mode is enabled while
*3
running.
Same as Pr.340 = "0".
key on the operation panel and the X65 signal.
5.9 (D) Operation command and frequency command
1
2
3
4
5
6
7
*3
8
9
10
399
5. PARAMETERS

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents